8
IO-Link interface: Parameters, commands and events (continued)
8.3

Profile-specific parameters

Index
Name
(dec)
0x003A
Teach-in
(58)
Channel
0x003B
Teach-in
(59)
Status
0x003C
Set Point
(60)
Value (BDC1)
0x003D
Switch Point
(61)
Configuration
(BDC1)
Tab. 8-3:
Profile-specific parameters
20
english
Subindex
Name
Data format
(dec)
0x00 (0)
0x00 (0)
0x01 (1)
Set Point SP1
0x02 (2)
Set Point SP2
0x01 (1)
Switch Point
Logic
0x02 (2)
Switch point
mode
0x03 (3)
Switch Point
Hysteresis
Access
Value range
(length)
UNIT8
RW
0x00 (0)
UNIT8
R
UINT16
R/W
0x0000...0xFFFF
(0...65535)
UINT16
R/W
0x0000...0xFFFF
(0...65535)
UINT8
R/W
0x00 = High
active
0x01 = Low
active
UINT8
R/W
0x01 = Single
Point (default)
0x03 = Two Point
Mode
UINT16
R/W
0x0000 = Stan-
dard Hysteresis
(default)
Description
BDC1 Standard
Proximity value in
ohms. The value is
automatically set in
the teach procedure.
Manual changes
may result in function
limitations.
Default is 10%
hysteresis. Default
cannot be changed