Temperature and humidity monitoring: Detects and collects statistics on the
ambient temperature and humidity inside the smart module; provides real-
time alarm signals.
Water leakage monitoring: Detects water leakage at the bottom of the smart
module and provides real-time alarm signals.
Smoke monitoring: Detects smoke in the smart module and provides real-
time alarm signals.
Power distribution monitoring:
a.
(In the intelligent power distribution scenario) Monitors the general
mains input voltage, frequency, current, and power, as well as the UPS
input voltage, frequency, current, and so on.
b.
(In the non-intelligent power distribution scenarios) Monitors the UPS
input voltage, frequency, current, and so on.
Smart cooling product monitoring:
a.
Monitors the supply and return air temperatures in real time.
b.
Allows you to set the return air temperature setpoint for a single product.
c.
Monitors and displays the fan speed, and displays the running
percentage.
d.
Monitors and displays the compressor running status.
Generates a 2.5D layout view that matches the actual layout of the smart
module, including the power distribution module, smart cooling product, and
T/H sensor. In addition, the resource usage rate of electric energy (displayed
only when the intelligent power distribution module is configured), ambient
temperature and humidity of the smart module are displayed on the home
screen of the app.
Displays the resource usage of the electric energy of the smart module and
each cabinet (displayed only when the intelligent power distribution module
is configured).
Displays the real-time status and alarms of the aisle temperature and
humidity sensor in the plan view.
Allows you to open the cabinet door on the corresponding screen after
logging in to the app installed on the PAD.
The system monitors the status of smart cooling products, power distribution,
and environment. If a fault or parameter error occurs, the system generates
an alarm in real time. You can view the alarm cause and solution in the alarm
details.
Alarms can be classified into four severities: critical, major, minor, and
warning. The alarm severities can be user-defined.