Outdoor
14.0 ℃ WB
air temp
20.0 ℃ DB
TC
PI
(℃DB)
kW
kW
-5
32.4
4.01
0
32.4
4.01
4
32.4
4.03
7
32.4
4.10
10
32.4
4.95
12
32.4
5.00
14
32.4
5.08
16
32.4
5.17
18
32.4
5.25
20
32.4
5.33
21
32.4
5.39
23
32.4
5.47
25
32.4
5.58
27
32.4
5.91
70%
29
32.4
6.27
31
32.4
6.63
33
32.4
7.05
35
32.4
7.46
37
32.4
7.87
39
32.4
8.34
41
30.6
9.40
43
28.9
9.80
44
28.5
10.22
46
27.4
12.5
47
26.9
13.60
50
24.6
13.35
52
19.3
10.49
53
16.1
8.73
55
15.1
8.17
-5
27.7
3.37
0
27.7
3.37
4
27.7
3.39
7
27.7
3.45
10
27.7
4.28
12
27.7
4.37
14
27.7
4.42
16
27.7
4.48
18
27.7
4.56
20
27.7
4.61
21
27.7
4.67
23
27.7
4.72
25
27.7
4.81
27
27.7
5.00
60%
29
27.7
5.28
31
27.7
5.61
33
27.7
5.91
35
27.7
6.27
37
27.7
6.63
39
27.7
6.99
41
26.2
7.90
43
24.8
8.24
44
24.4
8.59
46
23.5
10.5
47
23.0
11.43
50
21.1
11.23
52
16.6
8.55
53
13.8
7.11
55
12.9
6.66
17.0 ℃ WB
18.0 ℃ WB
24.0 ℃ DB
26.0 ℃ DB
TC
PI
TC
PI
kW
kW
kW
kW
38.5
4.96
44.9
6.01
38.5
4.96
44.9
6.02
38.5
4.98
44.9
6.04
38.5
5.08
44.9
6.15
38.5
5.86
44.9
6.82
38.5
5.94
44.9
6.96
38.5
6.05
44.9
7.07
38.5
6.16
44.9
7.21
38.5
6.27
44.9
7.35
38.5
6.38
44.9
7.49
38.5
6.44
44.9
7.54
38.5
6.55
44.9
7.71
38.5
6.82
44.9
8.21
38.5
7.27
44.9
8.76
38.5
7.71
44.9
9.31
38.5
8.18
44.9
9.92
38.5
8.70
44.9
10.55
38.5
9.23
44.9
11.19
38.5
9.78
44.9
11.91
38.5
10.36
44.9
12.63
36.6
11.63
42.6
14.10
35.5
12.13
41.1
14.86
34.7
12.64
40.6
15.67
33.9
15.4
39.7
16.2
33.5
16.82
39.2
16.45
30.0
16.52
35.0
17.34
26.0
13.06
32.2
14.56
21.4
10.74
2.7
12.70
19.5
9.79
2.5
11.54
33.0
4.11
38.4
4.93
33.0
4.12
38.4
4.93
33.0
4.13
38.4
4.95
33.0
4.21
38.4
5.04
33.0
5.03
38.4
5.83
33.0
5.11
38.4
5.94
33.0
5.19
38.4
6.02
33.0
5.28
38.4
6.13
33.0
5.36
38.4
6.24
33.0
5.47
38.4
6.35
33.0
5.50
38.4
6.41
33.0
5.61
38.4
6.52
33.0
5.72
38.4
6.77
33.0
6.05
38.4
7.21
33.0
6.41
38.4
7.68
33.0
6.82
38.4
8.15
33.0
7.21
38.4
8.65
33.0
7.65
38.4
9.17
33.0
8.10
38.4
9.73
33.0
8.56
38.4
10.31
31.4
9.64
36.5
11.56
29.8
10.05
35.5
12.18
29.7
10.48
34.8
12.84
29.1
12.8
34.0
13.3
28.7
13.95
33.6
13.48
25.8
13.70
30.0
14.22
22.3
10.65
27.6
11.98
18.3
8.76
24.1
10.45
16.7
7.99
21.9
9.50
GMV6 DC Inverter VRF Units
Indoor air temp
19.0 ℃ WB
20.0 ℃ WB
27.0 ℃ DB
28.0 ℃ DB
TC
PI
TC
kW
kW
kW
47.9
6.59
51.1
47.9
6.60
51.1
47.9
6.62
51.1
47.9
6.75
51.1
47.9
7.35
51.0
47.9
7.49
51.0
47.9
7.60
51.0
47.9
7.76
51.0
47.9
7.90
51.0
47.9
8.04
51.0
47.9
8.12
51.0
47.9
8.40
51.0
47.9
8.98
51.0
47.9
9.56
51.0
47.9
10.19
51.0
47.9
10.83
51.0
47.9
11.52
51.0
47.9
12.27
51.0
47.1
13.04
51.0
46.4
13.84
51.0
45.6
14.23
48.5
44.7
15.13
46.1
43.6
16.07
46.6
42.6
16.2
45.5
42.1
16.31
44.9
37.5
17.66
40.0
35.4
15.43
35.6
30.6
13.34
31.2
27.0
11.78
28.2
41.1
5.37
43.8
41.1
5.38
43.8
41.1
5.40
43.8
41.1
5.50
43.8
41.1
6.24
43.7
41.1
6.35
43.7
41.1
6.46
43.7
41.1
6.58
43.7
41.1
6.69
43.7
41.1
6.82
43.7
41.1
6.88
43.7
41.1
7.02
43.7
41.1
7.35
43.7
41.1
7.85
43.7
41.1
8.34
43.7
41.1
8.87
43.7
41.1
9.42
43.7
41.1
10.00
43.7
40.4
10.61
43.7
39.8
11.24
43.7
39.1
11.60
41.6
38.3
12.33
40.4
37.4
13.10
39.9
36.5
13.2
39.0
36.1
13.30
38.5
32.2
14.40
34.3
30.4
12.58
30.5
26.3
10.88
26.7
23.2
9.60
24.2
Technical Sales Guide
22.0 ℃ WB
24.0 ℃ WB
30.0 ℃ DB
32.0 ℃ DB
PI
TC
PI
TC
kW
kW
kW
kW
7.18
57.2
8.46
63.6
7.19
57.2
8.47
63.6
7.22
57.2
8.50
63.6
7.35
57.2
8.66
63.6
7.87
57.3
8.95
63.6
8.01
57.3
9.12
63.6
8.15
57.3
9.28
63.6
8.32
57.3
9.45
63.6
8.45
57.3
9.64
63.6
8.62
57.3
9.84
63.6
8.70
57.3
9.95
63.6
9.14
57.3
10.69
63.6
9.75
57.3
11.44
63.6
10.42
57.3
12.21
63.6
11.08
57.3
13.01
63.6
11.80
57.3
13.87
63.6
12.57
57.3
14.78
63.6
13.37
57.3
15.75
63.6
14.23
57.3
16.77
63.6
15.11
57.3
17.82
63.6
15.51
54.6
18.27
60.6
16.09
53.6
18.73
58.9
16.71
52.5
19.21
58.5
17.4
51.3
20.2
57.2
17.78
50.7
20.63
56.6
18.99
45.3
22.05
50.9
36.5
14.72
38.5
14.92
13.05
32.4
13.06
33.6
11.84
29.6
11.95
31.0
5.83
49.2
6.81
54.5
5.84
49.2
6.82
54.5
5.86
49.2
6.85
54.5
5.97
49.2
6.97
54.5
6.66
49.1
7.54
54.5
6.77
49.1
7.68
54.5
6.91
49.1
7.82
54.5
7.02
49.1
7.96
54.5
7.16
49.1
8.10
54.5
7.29
49.1
8.26
54.5
7.35
49.1
8.34
54.5
7.49
49.1
8.68
54.5
7.96
49.1
9.26
54.5
8.48
49.1
9.86
54.5
9.03
49.1
10.53
54.5
9.61
49.1
11.19
54.5
10.22
49.1
11.91
54.5
10.86
49.1
12.68
54.5
11.52
49.1
13.48
54.5
12.24
49.1
14.31
54.5
12.60
46.8
14.71
52.0
13.07
46.2
15.08
50.9
13.57
45.0
15.47
50.2
14.2
44.0
16.2
49.1
14.44
43.5
16.61
48.5
15.42
38.8
17.75
43.6
12.16
31.3
12.00
33.0
10.64
27.7
10.65
28.8
9.65
25.4
9.75
26.6
PI
kW
9.84
9.85
9.89
10.07
10.06
10.25
10.44
10.64
10.86
11.16
11.55
12.38
13.23
14.15
15.11
16.11
17.18
18.32
19.51
20.78
21.25
21.79
22.35
23.4
24.00
25.09
15.11
13.16
12.16
7.86
7.88
7.91
8.05
8.45
8.59
8.76
8.92
9.09
9.28
9.37
9.97
10.64
11.36
12.13
12.90
13.76
14.64
15.58
16.58
16.99
17.43
17.86
18.7
19.18
20.06
12.32
10.73
9.91
59

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents