BGH GMV6 Technical Sales Manual page 102

Table of Contents

Advertisement

Outdoor air
temp
℃ DB
℃ WB
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-13.7
-15.0
-11.8
-13.0
-9.8
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
70%
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7
18.0
16.8
20.0
18.5
24.0
20.5
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-13.7
-15.0
-11.8
-13.0
-9.8
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
60%
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7
18.0
16.8
20.0
18.5
24.0
20.5
100
16
18
TC
PI
TC
PI
kW
kW
kW
kW
47.7
25.35
47.6
25.99
62.2
32.80
58.1
31.35
62.2
32.09
58.2
30.66
62.4
31.35
58.3
30.05
62.4
30.61
58.3
29.17
62.4
29.73
58.4
28.09
62.5
29.26
58.4
27.29
62.5
28.83
58.4
26.55
62.4
27.48
58.3
25.31
62.0
25.67
57.9
23.68
62.0
24.17
57.9
22.32
62.0
22.00
57.9
20.44
62.0
20.10
57.9
0.45
62.0
18.97
57.9
17.57
62.0
17.93
57.9
16.63
62.0
16.95
57.9
15.72
62.0
16.04
57.9
14.88
62.0
15.15
57.9
14.09
62.0
14.35
57.9
13.36
62.0
14.32
57.9
13.33
62.0
14.27
57.9
13.28
62.0
14.21
57.9
13.22
48.2
27.29
45.9
26.60
53.4
29.97
49.8
28.46
53.4
29.22
49.8
27.32
53.5
28.28
49.9
26.00
53.5
26.77
49.9
24.63
53.6
25.33
50.0
23.32
53.6
24.63
50.0
22.69
53.6
23.98
50.0
22.11
53.5
22.89
49.9
21.12
53.2
21.43
49.6
19.78
53.2
20.23
49.6
18.69
53.2
18.48
49.6
17.12
53.2
16.95
49.6
15.72
53.2
16.03
49.6
14.87
53.2
15.17
49.6
14.08
53.2
14.37
49.6
13.36
53.2
13.64
49.6
12.69
53.2
12.90
49.6
12.02
53.2
12.28
49.6
11.41
53.2
12.25
49.6
11.39
53.2
12.21
49.6
11.35
53.2
12.16
49.6
11.30
Indoor air temperature ℃ DB
20
21
TC
PI
TC
PI
kW
kW
kW
kW
47.4
25.86
47.1
26.11
54.0
29.24
52.0
28.60
54.1
28.56
52.1
27.93
54.2
27.87
52.2
224.88
54.2
26.60
52.2
25.66
54.3
25.20
52.2
24.30
54.3
24.49
52.3
23.62
54.3
23.85
52.3
23.00
54.2
22.79
52.2
22.00
53.9
21.36
51.9
20.59
53.9
20.17
51.9
19.45
53.9
18.43
51.9
17.79
53.9
16.92
51.9
16.33
53.9
16.02
51.9
15.46
53.9
15.15
51.9
14.64
53.9
14.36
51.9
13.87
53.9
13.63
51.9
13.17
53.9
12.89
51.9
12.49
53.9
12.25
51.9
11.87
53.9
12.22
51.9
11.84
53.9
12.18
51.9
11.80
53.9
12.12
51.9
11.75
43.1
24.30
41.8
23.51
46.3
25.57
44.6
24.56
46.4
24.45
44.6
23.49
46.5
23.31
44.7
22.41
46.5
22.13
44.7
21.28
46.5
21.01
44.8
20.18
46.5
20.44
44.8
19.66
46.5
19.94
44.8
19.17
46.5
19.06
44.7
18.34
46.2
17.91
44.5
17.22
46.2
17.01
44.5
16.32
46.2
15.55
44.5
14.98
46.2
14.33
44.5
13.79
46.2
13.57
44.5
13.09
46.2
12.87
44.5
12.42
46.2
12.23
44.5
11.80
46.2
11.64
44.5
11.22
46.2
11.05
44.5
10.66
46.2
10.52
44.5
10.16
46.2
10.50
44.5
10.13
46.2
10.46
44.5
10.10
46.2
10.42
44.5
10.06
22
24
TC
PI
TC
PI
kW
kW
kW
kW
46.5
26.22
45.1
25.95
49.9
27.93
45.8
25.80
50.0
27.18
45.8
24.65
50.1
25.90
45.9
23.49
50.1
24.57
45.9
22.27
50.2
23.26
46.0
21.12
50.2
22.63
46.0
20.55
50.2
22.05
46.0
20.03
50.1
21.07
45.9
19.15
49.8
19.73
45.7
17.97
49.8
18.65
45.7
16.99
49.8
17.08
45.7
15.58
49.8
15.68
45.7
14.31
49.8
14.86
45.7
13.55
49.8
14.07
45.7
12.86
49.8
13.34
45.7
12.19
49.8
12.66
45.7
11.59
49.8
11.99
45.7
11.01
49.8
11.40
45.7
10.48
49.8
11.37
45.7
10.46
49.8
11.33
45.7
10.42
49.8
11.29
45.7
10.38
40.1
22.51
36.8
20.44
42.9
23.57
39.3
21.35
43.0
22.55
39.3
20.45
43.0
21.52
39.4
19.51
43.0
20.44
39.4
18.56
43.1
19.40
39.4
17.64
43.1
18.88
39.5
17.15
43.1
18.41
39.5
16.75
43.0
17.62
39.4
16.05
42.8
16.55
39.1
15.09
42.8
15.68
39.1
14.29
42.8
14.40
39.1
13.14
42.8
13.29
39.1
0.53
42.8
12.59
39.1
11.52
42.8
11.97
39.1
10.94
42.8
11.36
39.1
10.42
42.8
10.80
39.1
9.93
42.8
10.27
39.1
9.44
42.8
9.81
39.1
9.01
42.8
9.78
39.1
8.98
42.8
9.75
39.1
8.95
42.8
9.71
39.1
8.91