BGH GMV6 Technical Sales Manual page 118

Table of Contents

Advertisement

Situation
Situation 3
Situation 4
Situation 5
NOTES:
a. The above installation space is based on the assumption of outdoor temperature of 35°C. If the
outdoor temperature has exceeded 35°C or heating load is high and all ODUs are operating in
extended-capacity, the space needed for the suction side shall be increased.
b. When dismantling and installing the unit, the operation might be affected by the barrier, increase the
distance between the unit and wall properly.
c. When two or several units are installed and placed, the operation might affect the adjacent units, the
distance "e" between two adjacent units is ≥100mm.
d. If the unit is installed in the space with four walls, wall height at both side of the unit shall have no
limit; wall height at return air side is below 500mm and at the front side is below 1,500mm.
e. If the wall has exceeded the above value, please increase space according to the following method.
116
A+B+C+D
a≥300
b≥100
c≥100
d≥500
e≥200
f≥600
a≥300
b≥100
c≥100
d≥100
e≥200
f≥500
a≥300
b≥500
c≥100
d≥500
e≥200
f≥900
A+B
-
-
-