BGH GMV6 Technical Sales Manual page 59

Table of Contents

Advertisement

Outdoor
14.0 ℃ WB
air temp
20.0 ℃ DB
TC
PI
(℃DB)
kW
kW
-5
50.9
7.14
0
50.9
7.15
4
50.9
7.18
7
50.9
7.31
10
50.9
7.82
12
50.9
7.98
14
50.9
8.12
16
50.9
8.26
18
50.9
8.43
20
50.9
8.59
21
50.9
8.68
23
50.9
9.09
25
50.9
9.67
27
50.9
10.33
110%
29
50.9
11.02
31
50.9
11.74
33
50.9
12.49
35
50.9
13.29
37
50.9
14.15
39
50.9
15.03
41
48.1
16.74
43
45.4
17.46
44
44.8
18.21
46
43.1
22.2
47
42.2
24.23
50
38.7
23.79
52
28.1
17.65
53
23.4
14.68
55
21.9
13.74
-5
46.2
6.24
0
46.2
6.25
4
46.2
6.28
7
46.2
6.39
10
46.2
7.07
12
46.2
7.17
14
46.2
7.29
16
46.2
7.45
18
46.2
7.62
20
46.2
7.74
21
46.2
7.82
23
46.2
8.02
25
46.2
8.53
27
46.2
9.11
100%
29
46.2
9.65
31
46.2
10.27
33
46.2
10.92
35
46.2
11.62
37
46.2
12.38
39
46.2
13.18
41
43.7
14.64
43
41.3
15.27
44
40.7
15.92
46
39.1
19.4
47
38.4
21.18
50
35.1
20.80
52
27.6
16.07
53
23.0
13.36
55
21.5
12.51
17.0 ℃ WB
18.0 ℃ WB
24.0 ℃ DB
26.0 ℃ DB
TC
PI
TC
PI
kW
kW
kW
kW
60.7
9.18
70.4
11.02
60.7
9.20
70.4
11.04
60.7
9.23
70.4
11.08
60.7
9.41
70.4
11.29
60.7
9.53
70.4
11.33
60.7
9.73
70.4
11.55
60.7
9.89
70.4
11.77
60.7
10.08
70.4
11.99
60.7
10.28
70.4
12.24
60.7
10.50
70.4
12.96
60.7
10.80
70.4
13.43
60.7
11.58
70.4
14.39
60.7
12.38
70.4
15.39
60.7
13.23
70.4
16.47
60.7
14.12
70.4
17.60
60.7
15.06
70.4
18.79
60.7
16.05
69.9
19.81
60.7
17.10
69.0
20.53
60.7
18.21
67.7
21.27
60.7
19.39
66.5
21.99
57.6
21.55
65.5
25.86
54.7
22.47
64.6
27.26
54.6
23.43
62.4
28.74
53.4
28.6
61.0
29.7
52.8
31.18
60.3
30.18
47.3
30.61
53.9
31.82
37.8
21.97
46.8
24.72
31.1
18.07
40.8
21.57
28.4
16.48
37.1
19.59
55.0
7.99
64.1
9.96
55.0
8.00
64.1
9.98
55.0
8.03
64.1
10.02
55.0
8.18
64.1
10.20
55.0
8.59
64.1
10.16
55.0
8.71
64.1
10.30
55.0
8.86
64.1
10.48
55.0
9.06
64.1
10.71
55.0
9.26
64.1
10.92
55.0
9.40
64.1
11.28
55.0
9.50
64.1
11.66
55.0
10.15
64.1
12.54
55.0
10.79
64.1
13.34
55.0
11.53
64.1
14.32
55.0
12.32
64.1
15.31
55.0
13.12
64.1
16.32
55.0
13.97
64.1
17.40
55.0
14.88
64.1
18.55
55.0
15.85
64.1
19.76
55.0
16.88
64.1
21.04
52.3
18.75
60.9
23.38
49.7
19.56
59.4
24.64
49.5
20.38
58.0
25.97
48.4
24.9
56.7
26.8
47.9
27.12
56.1
27.27
42.9
26.63
50.0
28.76
37.2
20.00
46.0
22.51
30.6
16.45
40.1
19.63
27.9
15.00
36.4
17.84
GMV6 DC Inverter VRF Units
Indoor air temp
19.0 ℃ WB
20.0 ℃ WB
27.0 ℃ DB
28.0 ℃ DB
TC
PI
TC
kW
kW
kW
75.3
11.08
80.2
75.3
11.10
80.2
75.3
11.14
80.2
75.3
11.35
80.2
75.3
12.24
80.2
75.3
12.49
80.2
75.3
12.71
80.2
75.3
12.96
80.2
75.3
13.32
80.2
75.3
14.31
79.0
75.3
14.84
78.5
75.3
15.91
77.3
75.3
17.05
76.3
74.1
17.76
75.1
73.1
18.48
74.1
71.9
19.20
72.9
70.9
19.92
71.9
69.7
20.64
70.7
68.7
21.36
69.5
67.5
22.10
68.5
66.2
23.94
67.2
65.0
25.45
66.0
63.4
27.04
64.5
61.9
27.3
63.0
61.2
27.45
62.2
54.6
29.72
55.5
51.5
25.96
51.8
44.6
22.45
45.3
39.3
19.81
41.1
68.0
11.01
72.9
68.0
11.03
72.9
68.0
11.07
72.9
68.0
11.27
72.9
68.0
10.97
72.9
68.0
11.12
72.9
68.0
11.32
72.9
68.0
11.58
72.9
68.0
11.80
72.9
68.0
12.42
72.9
68.0
12.85
72.9
68.0
13.81
72.9
68.0
14.69
72.9
68.0
15.77
72.9
68.0
16.86
72.6
68.0
18.17
71.7
68.0
19.23
70.4
68.0
20.50
69.2
67.3
21.24
68.3
66.3
21.94
66.7
65.1
23.78
65.8
63.9
25.27
65.0
62.3
26.85
63.2
60.9
27.1
61.7
60.1
27.26
60.9
53.6
29.52
54.3
50.6
23.63
50.9
43.8
20.43
44.5
38.6
18.04
40.4
Technical Sales Guide
22.0 ℃ WB
24.0 ℃ WB
30.0 ℃ DB
32.0 ℃ DB
PI
TC
PI
TC
kW
kW
kW
kW
11.14
86.4
11.25
88.2
11.16
86.4
11.27
88.2
11.20
86.4
11.31
88.2
11.41
86.4
11.52
88.2
13.18
86.3
13.98
88.3
13.43
85.4
13.92
87.1
13.68
84.1
13.92
86.1
13.95
83.1
14.01
84.9
14.62
81.9
14.73
83.9
15.33
80.9
15.44
82.7
15.69
80.2
15.80
82.2
16.38
79.2
16.55
80.9
17.10
78.0
17.27
80.0
17.82
77.0
17.99
78.7
18.57
75.8
18.73
77.8
19.28
74.8
19.45
76.5
20.00
73.6
20.20
75.6
20.75
72.4
20.94
74.3
21.47
71.4
21.69
73.1
22.21
70.2
22.43
72.1
24.07
68.9
24.29
70.9
24.99
67.7
24.91
69.6
25.94
66.3
25.55
68.4
27.0
64.8
26.8
66.9
27.60
64.1
27.43
66.2
29.46
57.2
29.32
59.5
53.0
24.76
56.0
25.10
21.96
47.0
21.97
48.8
19.91
43.1
20.11
45.1
11.06
81.9
11.16
86.5
11.08
81.9
11.18
86.5
11.13
81.9
11.23
86.5
11.33
81.9
11.43
86.5
11.85
81.9
13.41
86.6
12.08
81.9
13.64
85.3
12.30
81.9
13.88
84.4
12.58
81.6
14.19
83.1
12.82
80.5
14.47
82.2
13.64
79.2
15.23
80.9
14.11
78.7
15.75
80.5
15.17
77.8
16.66
79.2
16.22
76.5
17.27
78.3
17.40
75.3
17.88
77.0
18.44
74.3
18.74
76.0
19.19
72.6
19.50
74.8
19.88
72.2
20.06
73.8
20.60
70.9
20.79
72.6
21.34
69.8
21.49
71.6
22.05
69.0
22.20
69.8
23.90
67.5
24.11
69.2
24.81
66.0
24.73
68.5
25.75
64.9
25.36
66.8
26.9
63.5
26.6
65.3
27.40
62.7
27.23
64.6
29.26
56.0
29.10
58.1
22.85
52.1
22.54
55.0
19.99
46.2
20.00
47.9
18.13
42.3
18.31
44.3
PI
kW
11.35
11.37
11.41
11.62
13.51
13.43
13.40
14.15
14.86
15.58
15.94
16.69
17.41
18.15
18.90
19.64
20.39
21.14
21.88
22.65
24.52
25.13
25.79
27.1
27.69
28.96
25.43
22.15
20.45
11.26
11.28
11.33
11.54
13.94
13.83
13.72
14.03
14.69
15.46
15.89
16.81
17.42
18.04
18.91
19.67
20.24
20.97
21.69
22.40
24.33
24.95
25.59
26.8
27.48
28.74
23.15
20.16
18.62
57

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents