Data Register List <Akw1110 - Panasonic KW1M Eco-Power METER User Manual

Table of Contents

Advertisement

7.4.3 Data Register List <AKW1110>
Data item
Name
(MEWTOCOL)
0036H
Rate (CHG)
(DT00054)
0037H
Conversion factor
(DT00055)
(CO2)
003CH
CT type
(DT00060)
003DH
(DT00061)
Unit for
Pulse output
003EH
(DT00062)
Primary side
003FH
current value
(DT00063)
when CT 5A
0040H
Power alarm value
(DT00064)
(Instantaneous
0041H
active power)
(DT00065)
0042H
VT ratio
(DT00066)
Current threshold
0043H
for time
(CT00067)
measurement
0044H
Cutoff current
(DT00068)
0045H
Current alarm value
(DT00069)
0064H
(DT00100)
Integrated electric
0065H
Power
(DT00101)
006BH
R-current
(DT00107)
006DH
T-current
(DT00109)
0096H
(DT00150)
Load ON-time
0097H
(DT00151)
0098H
(DT00152)
Load OFF-time
0099H
(DT00153)
00A3H
Auto-off time
(DT00163)
00AAH
(DT00170)
R(RS)-voltage
00ABH
(DT00171)
00AEH
(DT00174)
T(TS)-voltage
00AFH
(DT00175)
Unit
Kind of date
0.01
Unsigned 16bit
0.001
Unsigned 16bit
2
kg-CO
Rated A
Unsigned 16bit
(rms)
Unsigned 32bit
1A
Unsigned 16bit
0.01kW
Unsigned 32bit
0.01
Unsigned 16bit
0.1%
Unsigned 16bit
0.1%
Unsigned 16bit
0.1%
Unsigned 16bit
0.01kWh Unsigned 32bit
0.1A
Unsigned 16bit
0.1A
Unsigned 16bit
0.1h
Unsigned 16bit
0.1h
Unsigned 16bit
min
Unsigned 16bit
0.1V
Unsigned 32bit
0.1V
Unsigned 32bit
39
KW1M Eco-POWER METER
Range: Hexadecimal
(Range: Decimal)
0H to 270FH (0 to 9999)
0H to 270FH (0 to 9999)
5 types:
5H(5), 32H(50), 64H(100),
FAH(250), 190H(400)
1H(1)
AH(10)
<0.001>,
<0.01>,
64H(
3E8H
100)<0.1>,
(1000)<1>,
2710H
(10000)<10>,
186A0H
(100000)<100>,
3E7H(999)
<Instantaneous electric power:
Values of 0040H,0041H>
309H(777)
<Ratio for current alarm:
Values of 0045H>
1H to FA0H
(1 to 4000)
0H to F423FH
(0 to 999999)
64H to 270FH
(100 to 9999)
1H to 3E8H
(1 to 1000)
AH to 1F4H
(10 to 500)
AH to 3E8H
(10 to 1000)
0H to 3B9AC9FFH
(0 to 999999999)
0H to EA60H (0 to 60000)
0H to EA60H(0 to 60000)
0H to F423FH
(0 to 999999)
0H to F423FH
(0 to 999999)
0H to 63H (0 to 99)
(0H:always on)
0H to F423FH (0 to 999999)
0H to F423FH (0 to 999999)
MODBUS
Function code
03H/06H/10H
03H/06H/10H
03H/06H/10H
03H/06H/10H
03H/06H/10H
03H/06H/10H
03H/06H/10H
03H/06H/10H
03H/06H/10H
03H/06H/10H
03H/06H/10H
03H
03H
03H/06H/10H
03H/06H/10H
03H/06H/10H
03H
03H

Advertisement

Table of Contents
loading

This manual is also suitable for:

Akw1111Akw1110

Table of Contents