E2S SONFL1XDC012 Instructions/Service Manual

E2S SONFL1XDC012 Instructions/Service Manual

High output alarm horn & xenon strobe beacon

Advertisement

Quick Links

 
INSTRUCTION & SERVICE MANUAL
SONFL1X-HO Range - High Output Alarm Horn & Xenon Strobe Beacon
 
SONFL1X-HO Combined Sounder & Xenon Beacon
10 Selectable Tones & 2 Stages
5J Xenon Flash Tube
Three Modes: Flashing 1Hz (AC & DC)
Flashing 1.5Hz and Double Strike (DC Units Only)
1Hz Flashing mode CPR / VdS approved
24Vdc version CPR / VdS approved
CE, EAC Approved
IP Rating: IP66
 
Model No.
Nominal Voltage
SONFL1XDC012...[X]/[Y]-H
12V dc
SONFL1XDC024...[X]/[Y]-H
24V dc
*Current at nominal voltage on Tone 2
[X] Denotes Housing Colour: R = Red; G = Grey; W = White
[Y] Denotes Lens Colour: A = Amber; B = Blue; C = Clear; G = Green; M = Magenta; R = Red; Y = Yellow
Note: CPR Approved Units only available with Clear Lens
 
5
0.5 - 1.5mm²
Use suitable conduit or cable glands with
suitable IP or type rating
Attention: Installation must be carried out by an electrician in compliance with the latest codes and regulations.
 
Attention: L'installation doit être effectuée par un électricien conformément aux derniers codes et réglementations.
Achtung: Die Installation muss von einem Elektriker gemäß den neuesten Vorschriften und Bestimmungen durchgeführt werden.
Attenzione: L'installazione deve essere eseguita da un elettricista in conformità con i codici e le normative più recenti.
Atención: La instalación debe ser realizada por un electricista de acuerdo con los últimos códigos y regulaciones.
Atenção: A instalação deve ser realizada por um eletricista de acordo com os códigos e regulamentos mais recentes.
Внимание: установка должна выполняться электриком в соответствии с последними нормами и правилами.
Attention: Disconnect from power source before installation or service to prevent electric shock
Attention: Débranchez-le de la source d'alimentation avant l'installation ou l'entretien pour éviter tout choc électrique.
Achtung: Vor Installation oder Wartung von der Stromquelle trennen, um einen Stromschlag zu vermeiden.
Attenzione: scollegare dall'alimentazione prima dell'installazione o dell'assistenza per evitare scosse elettriche.
Atención: desconéctelo de la fuente de alimentación antes de la instalación o el servicio para evitar descargas eléctricas.
Atenção: Desconecte da fonte de alimentação antes da instalação ou serviço para evitar choque elétrico
Внимание: отключите от источника питания перед установкой или обслуживанием, чтобы предотвратить поражение
электрическим током.
No liability is accepted for any consequences of the use of this document. The technical specifica on of this unit is subject to change without no ce due to our policy of con nual 
product development. All dimensions/weights are approximate. This unit is sold subject to our standard condi ons of sale, a copy of which is available on request. 
E2S Warning Signals
Impress House, Mansell Road, Acton, London W3 7QH
 
Dimensions: 172 x 86 x 83mm
Cable Entry: 2-off M20 x 1.5mm
Temp: -40°C to +55°C
Unit weight: 0.46Kg
SONFL1X-HO
 
Sound Pressure Level dB(A)
Horn Nom.
Beacon Nom.
Voltage Range
Current
Current
Max
10-14V dc
50mA
500mA
105.0 @ 1m
96.0 @ 3m
20-28V dc
80mA*
250mA
 
Terminal Connections
 
sales@e2s.com
e2s.com
 
See D242-06-501 - Schematic Wiring
Volume
Control
Tone Selection
(See Table)
Nominal
103.0 @ 1m
94.0 @ 3m
 
0.4Nm
Page 1 of 3
DC Circuit
+
-
BEACON
S2
PCBA
SWITCH
S2 Denotes Stage 2
+
-
Stage switches are
customer supplied
+
DC
-
+
-
+ve IN
+
+
-ve IN
-
-
Stage 2
S2
Stage 1: Apply Power to +ve & -ve
Stage 2: Apply Power to +ve & -ve & connect Stage 2 to -ve
Beacon pre-wired to Alarm terminals by default
Note: Stage 2 is not VdS Approved
D242-00-511-IS_Issue_1 - 26/04/2021

Advertisement

loading

Summary of Contents for E2S SONFL1XDC012

  • Page 1 Внимание: отключите от источника питания перед установкой или обслуживанием, чтобы предотвратить поражение электрическим током. Note: Stage 2 is not VdS Approved No liability is accepted for any consequences of the use of this document. The technical specifica on of this unit is subject to change without no ce due to our policy of con nual  product development. All dimensions/weights are approximate. This unit is sold subject to our standard condi ons of sale, a copy of which is available on request.  E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com e2s.com Page 1 of 3...
  • Page 2 1.5Hz Flash (90FPM) backboxes to maintain IP rating Header Pin settings Double Strike Flash Pattern for flashing modes. 98,0 [3,86] E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com e2s.com Page 2 of 3 D242-00-511-IS_Issue_1 - 26/04/2021...
  • Page 3 (TESTING AT MINIMUM VOLTAGE OF 18V DC. ALL READINGS ARE IN dB(A) @ 1m) SONFL1XDC024-H HORIZONTAL POLAR PLOT SONFL1XDC024-H VERTICAL POLAR PLOT     E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com e2s.com Page 3 of 3...

This manual is also suitable for:

Sonfl1xdc024Sonfl1 seriesSonfl1xdc012 seriesSonfl1xdc024 seriesSonfl1xac024 seriesSonfl1xac115 series ... Show all