HRS
Series
Option symbol
G

High-temperature Environment Specifications

HRS
A
20 G
Makes use at ambient temperatures up to 45°C possible.
Also increases cooling capacity at ambient temperature of 32°C.
(Cooling capacity is equal to standard products at ambient
temperatures of less than 32°C.)
HRS012/018/024-A-20-G
Applicable model
Cooling method
Power supply
Single-phase 200 to 230 VAC (50/60 Hz)
∗ No change in external dimensions
∗ HRS030/050/060 cannot be selected.
Note 1) If the product is used at altitude of 1000 m or higher, refer to "Operating Environment/Storage Environment"(page 41)
Cooling Capacity
Note 2) For a product with high-pressure pump option (-T), the cooling capacity will decrease by about 300 W from each graph.
HRS012-A
-20-G
2500
2000
1500
1100
1000
500
0
0
10
Circulating fluid temperature [°C]
HRS018-A
-20-G
2500
2000
1700
1500
1000
500
0
0
10
Circulating fluid temperature [°C]
HRS024-A
-20-G
3500
3000
2500
2100
2000
1500
1000
500
0
0
10
Circulating fluid temperature [°C]
25
High-temperature environment specifications
Air-cooled refrigeration
Item 14 "∗ For altitude of 1000 m or higher".
Ambient
25°C
32°C
40°C
45°C
20
30
40
Ambient 25°C
32°C
40°C
45°C
20
30
40
Ambient 25°C
32°C
40°C
45°C
20
30
40
Note) Options have to be selected when
[50 Hz]
2500
2000
1500
1300
1000
500
0
50
0
[50 Hz]
2500
2000
1900
1500
1000
500
0
50
0
[50 Hz]
3500
3000
2500
2400
2000
1500
1000
500
0
50
0
ordering the thermo-chiller. It is
not possible to add them after
purchasing the unit.
Ventilation slots are added to
side panels (on both sides).
∗Ventilation slots are added to thermo-
chiller side panels. For this reason,
please provide 300 mm of ventilation
space next to the side panels (do not
install with sides touching walls).
Ambient
25°C
32°C
45°C
10
20
30
Circulating fluid temperature [°C]
Ambient 25°C
32°C
45°C
10
20
30
Circulating fluid temperature [°C]
Ambient 25°C
32°C
45°C
10
20
30
Circulating fluid temperature [°C]
[60 Hz]
40°C
40
50
[60 Hz]
40°C
40
50
[60 Hz]
40°C
40
50