Typical Power Cable Sizes - ABB ACS380 Hardware Manual

Hide thumbs Also See for ACS380:
Table of Contents

Advertisement

146 Technical data
Type
Typical power loss
ACS380-
04xx-...
04A0-4
62
05A6-4
91
07A2-4
100
09A4-4
140
12A6-4
165
17A0-4
259
25A0-4
390
032A-4
396
038A-4
497
045A-4
582
050A-4
672
1) Typical drive losses when it operates at 90% of the motor nominal frequency and 100% of the drive nominal
output current.

Typical power cable sizes

The table in this section gives the typical power cable and conductor sizes for use at
the nominal drive current.
Note: IEC/EN 61800-5-1 requires two separate PE (ground) conductors for a fixed
connection, if the cross-sectional area of the PE conductor is less than 10 mm
Cable size, Cu (mm 2 )
Type
ACS380-
04xx-...
1-phase U N = 230 V
02A4-1
03A7-1
04A8-1
06A9-1
07A8-1
09A8-1
12A2-1
3-phase U N = 230 V
02A4-2
03A7-2
04A8-2
06A9-2
07A8-2
09A8-2
1)
W
BTU/h
212
311
341
478
563
884
1331
1351
1696
1986
2293
3×1.5 + 1.5
3×1.5 + 1.5
3×1.5 + 1.5
3×1.5 + 1.5
3×1.5 + 1.5
3×2.5 + 2.5
3×2.5 + 2.5
3×1.5 + 1.5
3×1.5 + 1.5
3×1.5 + 1.5
3×1.5 + 1.5
3×1.5 + 1.5
3×2.5 + 2.5
Air flow
m 3 /h
CFM
57
57
57
57
63
128
128
150
150
150
150
1)
Conductor size, Cu (AWG)
Noise
dB(A)
33
63
33
63
33
63
33
63
37
59
75
66
75
66
88
69
88
69
88
69
88
69
16
16
16
16
16
14
14
16
16
16
16
16
14
Frame
size
R1
R1
R1
R1
R2
R3
R3
R4
R4
R4
R4
2
Cu.
Frame
size
R0
R0
R1
R1
R1
R2
R2
R1
R1
R1
R1
R1
R1