READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
THERMOSTAT.
•
Failure to observe safety information and comply with instruc-
tions could result in PERSONAL INJURY, DEATH AND/OR
PROPERTY DAMAGE.
▲
•
To avoid electrical shock or damage to equipment, disconnect
power before installing or servicing and use only wiring with
!
insulation rated for full thermostat operating voltage.
•
Before installing this control, the Voltage Selection Switch must
be placed in the correct position. See instructions.
•
To avoid potential fire and/or explosion do not use in potentially
flammable or explosive atmospheres.
•
Retain these instructions for future reference. This product,
when installed, will be part of an engineered system whose
specifications and performance characteristics are not designed
or controlled by PECO. You must review your application and
national and local codes to assure that your installation will be
functional and safe.
CAUTION
•
Use copper wire only, insulate or wire nut all unused leads.
▲
•
Care should be used to avoid electrostatic discharge to the T180
!
thermostat.
•
This unit has configuration jumpers. You may need to reconfigure
this thermostat for your application.
applications and features
For 2 or 4 Pipe Fan Coil and On/Off Control Applications
•
7 Day, 4 Event Programmability
•
System Selection: Off-Heat-Cool-Auto-Setback
•
6 Outputs: 1H, 1C, Up to 3 Fan, OA Damper
•
Fan Control: 1-3 Speeds
Cycling (Auto) or Continuous (On)
Automatic Fan Speed Staging
Connections for:
•
Fan Coil Pipe Sensor
•
Remote Temperature Probe
•
Occupancy Control
•
Door Switch or Setback
•
Condensate Overflow
specifications
Temperature Set Point Range
Differential
Memory – Back-Up
Mounting
© COPYRIGHT 2008 PECO, INC. ALL RIGHTS RESERVED.
WARNING
!
(TB180 models only)
SYSTEM
FAN
PROGRAM
50 to 90°F / 10 to 32°C
1°
EEPROM, No batteries required,
Stores settings for unlimited time
Installs on standard 4" x 4"
device box with a 2" x 4"
horizontal mud ring
TA/TB180 THERMOSTAT
Physical Dimensions
Agency Approvals
Electrical Ratings
VOLTAGE
FLA
24 VAC
NA
120 VAC
5.8
240 VAC
2.9
277 VAC
2.4
COMBINED LOAD CURRENT NOT TO EXCEED 20 AMPS
installation
New Installations
The thermostat should be used indoors only. It should be mounted on
an inner wall in a location with freely circulating air, and where it will be
responsive to changes in room temperature. Avoid mounting near heat
generating appliances (i.e. TV, heater, refrigerator), or in direct sunlight.
Remove Old Thermostat
1.
Turn off power to thermostat at main fuse or circuit breaker box.
Ensure that ALL power is disconnected. to prevent electrical
shock and /or equipment damage, disconnect electrical
power to the system at the main fuse or circuit breaker until
installation is complete.
2.
Remove the front cover of old thermostat. With wires still attached,
remove wall plate from the wall. If the old thermostat has a wall
mounting plate, remove the thermostat and the wall mounting plate
as an assembly.
3.
Before removing wires from old thermostat, label each wire
with the terminal designation from which it was attached.
4.
Disconnect the wires from the old thermostat one at a time. do not
let wires fall back into the wall.
Jumper and Circuit Board Selections
Voltage selection switch: This switch must be placed in the appropriate
position prior to application of power.
•
24V
= 24 VAC
•
110-277 V
= 120, 240 or 277 VAC
Jp1 Jumper selection – remote temperature sensor:
•
Local Sensing – Install JP1
•
Remote Sensing – Remove JP1 – Accessory sensors are available
in standard 60" lengths but can be extended to meet application
requirements.
4.4"H x 5.8"W x 1.1"D
UL, UL Canada
(see table below)
RATINGS
RES
PILOT
AMPS
DUTY
LRA
NA
NA
24 VA
34.8
6.0
125 VA
17.4
5.0
125 VA
14.4
4.2
125 VA
P/N 69387 3220-2124 REV 0 PAGE 1
HP
NA
1/4
1/4
1/4
▲
!