READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
THERMOSTAT.
Failure to observe safety information and comply with instruc-
tions could result in PERSONAL INJURY, DEATH AND/OR
PROPERTY DAMAGE.
To avoid electrical shock or damage to equipment, disconnect
power before installing or servicing and use only wiring with
!
insulation rated for full thermostat operating voltage.
Before installing this control, the Voltage Selection Switch must
be placed in the correct position. See instructions.
To avoid potential fire and/or explosion do not use in potentially
flammable or explosive atmospheres.
Retain these instructions for future reference. This product,
when installed, will be part of an engineered system whose
specifications and performance characteristics are not designed
or controlled by PECO. You must review your application and
national and local codes to assure that your installation will be
functional and safe.
CAUTION
Use copper wire only, insulate or wire nut all unused leads.
Care should be used to avoid electrostatic discharge to the T180
!
thermostat.
This unit has configuration jumpers. You may need to reconfigure
this thermostat for your application.
applications and features
For 2 or 4 Pipe Fan Coil and On/Off Control Applications
7 Day, 4 Event Programmability
System Selection: Off-Heat-Cool-Auto-Setback
6 Outputs: 1H, 1C, Up to 3 Fan, OA Damper
Fan Control: 1-3 Speeds
Cycling (Auto) or Continuous (On)
Automatic Fan Speed Staging
Connections for:
Fan Coil Pipe Sensor
Remote Temperature Probe
Occupancy Control
Door Switch or Setback
Condensate Overflow
specifications
Temperature Set Point Range
Differential
Memory – Back-Up
Mounting
© COPYRIGHT 2008 PECO, INC. ALL RIGHTS RESERVED.
WARNING
!
(TB180 models only)
SYSTEM
FAN
PROGRAM
50 to 90°F / 10 to 32°C
EEPROM, No batteries required,
Stores settings for unlimited time
Installs on standard 4" x 4"
device box with a 2" x 4"
horizontal mud ring
TA/TB180 THERMOSTAT
Physical Dimensions
Agency Approvals
Electrical Ratings
VOLTAGE
FLA
24 VAC
NA
120 VAC
5.8
240 VAC
2.9
277 VAC
2.4
COMBINED LOAD CURRENT NOT TO EXCEED 20 AMPS
installation
New Installations
The thermostat should be used indoors only. It should be mounted on
an inner wall in a location with freely circulating air, and where it will be
responsive to changes in room temperature. Avoid mounting near heat
generating appliances (i.e. TV, heater, refrigerator), or in direct sunlight.
Remove Old Thermostat
1.
Turn off power to thermostat at main fuse or circuit breaker box.
Ensure that ALL power is disconnected. to prevent electrical
shock and /or equipment damage, disconnect electrical
power to the system at the main fuse or circuit breaker until
installation is complete.
2.
Remove the front cover of old thermostat. With wires still attached,
remove wall plate from the wall. If the old thermostat has a wall
mounting plate, remove the thermostat and the wall mounting plate
as an assembly.
3.
Before removing wires from old thermostat, label each wire
with the terminal designation from which it was attached.
4.
Disconnect the wires from the old thermostat one at a time. do not
let wires fall back into the wall.
Jumper and Circuit Board Selections
Voltage selection switch: This switch must be placed in the appropriate
position prior to application of power.
24V
= 24 VAC
110-277 V
= 120, 240 or 277 VAC
Jp1 Jumper selection – remote temperature sensor:
Local Sensing – Install JP1
Remote Sensing – Remove JP1 – Accessory sensors are available
in standard 60" lengths but can be extended to meet application
requirements.
4.4"H x 5.8"W x 1.1"D
UL, UL Canada
(see table below)
RATINGS
RES
PILOT
AMPS
DUTY
LRA
NA
NA
24 VA
34.8
6.0
125 VA
17.4
5.0
125 VA
14.4
4.2
125 VA
P/N 69387 3220-2124 REV 0 PAGE 1
HP
NA
1/4
1/4
1/4
!

Advertisement

loading

Summary of Contents for Peco TA180

  • Page 1 Remove Old Thermostat or controlled by PECO. You must review your application and Turn off power to thermostat at main fuse or circuit breaker box. national and local codes to assure that your installation will be Ensure that ALL power is disconnected.
  • Page 2 Switch Switch White/Violet White/Violet After wiring and installation is complete, energize the system. Set fan to ON. Select each fan speed (TA180 Models) to verify operation. Setback Input/ Door Switch White/Black Set the System button to AUTO, or available selection.
  • Page 3 This mode is an energy saving feature that minimizes heating and cooling when the room is not Pipe Sensor Input: 10K PECO Remote Probe or a standard On-Off Aqua- occupied. The thermostat will control to the SETBACK Heat ©...
  • Page 4 HVAC system to control at setback limits. Occupancy Operation – Install JP3 The T180 can be used with PECO S200 series occupancy detection equipment. The occupancy and switch inputs are designed to connect to the SB200 slave sensor and SE200 door switch.

This manual is also suitable for:

Tb180