ABB SPAU 140 C User Manual And Technical Description page 15

Synchro-check relay
Table of Contents

Advertisement

Mode of operation
Command mode or continuous mode operation
Command mode operation
Max. close signal length t
command mode operation
Setting range
Time permitted for checking and request
for CB closing t
CHECK
Setting range
Data transmission
Transmission mode
Data code
Data transfer rates
Bus connection module without external supply
- for plastic core cables
- for glass fibre cables
Bus connection module with external supply
- for plastic core cables
- for glass fibre cables
Test voltages
Insulation test voltage, inputs and outputs
between themselves and to the relay frame as
per IEC 255-5 and SS 436 15 03
Impulse test voltage, inputs and outputs
between themselves and to the relay frame as
per IEC 255-5 and SS 436 15 03
Insulation resistance as per IEC 255-5
Disturbance tests
High frequency interference test voltage,
inputs and outputs between themselves
and to the relay frame as per IEC 255-22-1
and SS 436 15 03
Fast transients as per IEC 255-22-4
Electrostatic discharge test as per IEC 255-22-2
Environmental conditions
Specified ambient service temperature range
Temperature influence on the operation values
of the relay over the specified ambient service
temperature range
Long term damp heat withstand according
to IEC 68-2-3
Transport and storage temperature range
Degree of protection by enclosure of relay case
according to IEC 529 at panel mounting
Weight of relay
at
PULSE
0.2...20 s
0.05...300 s
Fibre-optic serial bus
ASCII
4800 Bd or 9600 Bd
SPA-ZC 21 BB
SPA-ZC 21 MM
SPA-ZC 17 BB
SPA-ZC 17 MM
2 kV, 50 Hz, 1 min
5 kV, 1.2/50 µs, 0.5 J
100 MΩ, 500 V dc
2.5 kV, 1 MHz
Class III, 2 kV
8 kV, 150 pF
-10...+55°C
<0.1%/°C
<95% at 40°C, 96 h
-40...+70°C
IP54
about 3.0 kg
15