Maintenance
and repairs
Exchange and
spare parts

Order numbers

Order data

18
When the synchro-check relay is used under the
conditions specified in "Technical data", it re-
quires practically no maintenance. The relay
includes no parts or components that are sensi-
tive to physical or electrical wear under normal
operating conditions.
Should the temperature and humidity at the
operating site differ from the values specified,
or the atmosphere contain chemically active
gases or dust, the relay should be visually in-
spected in association with the secondary test-
ing of the relay. This visual inspection should
focus on:
- Signs of mechanical damage to relay case and
terminals
- Collection of dust inside the relay case; remove
with compressed air
- Signs of corrosion on terminals, case or inside
the relay
Synchro-check relay module
Power and output relay module
- U
= 80...265 V ac/dc
aux
- U
= 18...80 V dc
aux
Relay case including I/O module
I/O module, as a separate unit
Bus connection module
Bus connection module
Synchro-check relay without test adapter
SPAU 140 C
Synchro-check relay with test adapter RTXP 18
SPAU 140 C
The last two letters indicate the rated frequency f
of the relay as follows:
AA: f
= 50 Hz and U
n
aux
CA: f
= 50 Hz and U
n
aux
DA: f
= 60 Hz and U
n
aux
FA: f
= 60 Hz and U
n
aux
Type
1. Quantity
2. Order number
3. Rated frequency
4. Auxiliary voltage
5. Accessories
6. Special requirements
If the relay malfunctions or the operating val-
ues differ from those specified, the relay should
be overhauled. Minor measures such as change
of a plug-in-type PC board can be taken by
normal service personnel with the required skill.
In uncertain cases and if the fault is permanent
the manufacturer or his nearest representative
should be contacted for further information
about checking, overhaul and recalibration of
the relay.
Note!
The protection relay contains circuits that are
sensitive to electrostatic discharge. If you have
to withdraw a relay module, ensure that you are
at the same potential as the module, for instance,
by touching the case.
Note!
Static protective relays are measuring instru-
ments and should be handled with care and pro-
tected against moisture and mechanical stress,
especially during transport.
SPCU 3D45
SPTU 240 R4
SPTU 48 R4
SPTK 3E10
SPTE 3E10
SPA-ZC 17_
SPA-ZC 21_
RS 488 001 -AA, CA, DA, FA
RS 488 201 -AA, CA, DA, FA
n
= 80...265 V ac/dc
= 18...80 V dc
= 80...265 V ac/dc
= 18...80 V dc
Example
15 relays SPAU 140 C
RS 488 001 - AA
f
U
15 connection modules SPA-ZC 21 MM
30 fibre-optic cables SPA-ZF MM 100
RS 426 005 -AA
RS 941 024 -AA
RS 941 024 -BA
and the auxiliary voltage U
= 50 Hz
n
= 110 V dc
aux
aux