ABB SPAU 140 C User Manual And Technical Description page 37

Synchro-check relay
Table of Contents

Advertisement

Output relay switch-
group SGR for alarm
signals
The alarms required in command mode opera-
tion are selected by means of switchgroup SGR.
Switch
Function
SGR/1
When SGR/1=1, the alarm signal NC13 of stage 1 for a failed CB closing
is delivered to the output relay ALARM and the corresponding operation
figure is indicated on the display.
When SGR/1=0, the alarm signal NC13 is blocked.
SGR/2
Switch is not in use. The switch should be in position 0.
SGR/3
When SGR/3=1, the alarm signal CSF13 of stage 1 for too long a
command signal CS13 is delivered to the output relay ALARM and
the corresponding operation figure is indicated on the display.
When SGR/3=0, the alarm signal CSF13 is blocked.
SGR/4
Switch is not in use. The switch should be in position 0.
SGR/5
When SGR/5=1, the alarm signal NC23 of stage 2 for a failed CB closing
is delivered to the output relay ALARM and the corresponding
operation figure is indicated on the display.
When SGR/5=0, the alarm signal NC23 is blocked.
SGR/6
Switch is not in use. The switch should be in position 0.
SGR/7
When SGR/7=1, the alarm signal CSF23 of stage 2 for excessive duration
of the command signal CS23 is delivered to the output relay ALARM and
the corresponding operation figure is indicated on the display.
When SGR/7=0, the alarm signal CSF23 is blocked.
SGR/8
Switch is not in use. The switch should be in position 0.
Checksum for factory setting
All alarm signals are delivered to the common
output relay ALARM.
Factory
defaults
0
0
0
0
0
0
0
0
0
17