Command Mode Operation - ABB SPAU 140 C User Manual And Technical Description

Synchro-check relay
Table of Contents

Advertisement

Settings for the
command mode
operation
10
cond13
CS13
BS13
CB13
NC13
Fig. 8. Determination of the checking time for closing.
Closing is permitted during the time t
ing from the moment when the external com-
mand signal CS13 is activated. The external
command signal has to be active during the
whole pre-set checking time, that is, when the
length of the external command signal to be de-
livered to the supervision stage is determined,
the value of the set t
check
ered too. If the closing command conditions get
fulfilled during the t
check
is delivered to the circuit breaker. If the closing
conditions are not fulfilled during the checking
time, the alarm NC13 is activated for 500 ms
as an indication of a failed closing attempt. If
the closing conditions do not become valid un-
til after the t
time, no closing signal is de-
check
The checking time t
check
after which closing of the circuit breaker is per-
mitted. The checking time starts after activa-
tion of the external command signal and the
signal shall be active during the total checking
time.
The maximum length of the closing signal in
the command mode operation is determined by
the set t
time.
pulse
t
check
500 ms
start-
check
time must be consid-
time, a closing signal
determines the time
livered. The closing signal is delivered only once
per activated external command signal. A new
closing command sequence cannot be started
until the external command signal has been re-
set and then activated again.
By removing the external command signal too
early the started closing command sequence can
be interrupted and the supervision stage can be
reset to original state. If the command signal
CS13 is removed before the checking time t
has elapsed and the closing operation has not
been enabled, the sequence resets and no alarm
of the failed closing attempt is delivered. The
activation of the external command signal again
starts a new checking sequence.
The closing signal may even be shorter depend-
ing on whether the external command signal
delivered to the stage is removed before the set
maximum t
time has elapsed.
pulse
The alarms in the command mode operation
are enabled or disabled by means of the func-
tional switchgroup SGR.
check