ABB SPAU 140 C User Manual And Technical Description page 35

Synchro-check relay
Table of Contents

Advertisement

Function selector
switches
Functional switch-
group SGF
Additional functions required by individual
applications are selected by means of switch-
groups SGF, SGB and SGR indicated on the
front panel. The numbering of the switches, i.e.,
1...8, and the switch positions 0 and 1, are in-
Switch Function
SGF/1 Selection of energizing direction for stage 1 in the voltage-check function.
SGF/2
SGF/1 SGF/2
0
0
1
0
0
1
1
1
SGF/3 Selection of synchro-check function of stage 1.
When SGF/3=1, the synchro-check function is enabled.
When SGF/3=0, the synchro-check function is disabled.
SGF/4 Selection of voltage-check function of stage 1.
When SGF/4=1, the voltage-check function is enabled.
When SGF/4=0, the voltage-check function is disabled.
SGF/5 Selection of energizing direction for stage 2 in the voltage-check function.
SGF/6
SGF/5 SGF/6
0
0
1
0
0
1
1
1
SGF/7 Selection of synchro-check function of stage 2.
When SGF/7=1, the synchro-check function is enabled.
When SGF/7=0, the synchro-check function is disabled.
SGF/8 Selection of voltage check function of stage 2.
When SGF/8=1, the voltage-check function is enabled.
When SGF/8=0, the voltage-check function is disabled.
Checksum for factory setting
dicated when the switches are set. Under nor-
mal service only the checksums are shown on
the display. The switchgroups SGF, SGB and
SGR are software-based and thus not to be
found in the hardware of the relay module.
Energizing direction
Both "de-energized" or U1→U3 or U1←U3
U1→U3
U1←U3
U1→U3 or U1←U3
Energizing direction
Both "de-energized" or U2→U3 or U2←U3
U2→U3
U2←U3
U2→U3 or U2←U3
Factory
defaults
1
1
0
0
1
1
0
0
51
15