13. Function I/O
13.2

Output function table

The configuration installed on ATS by Legrand, ensures the correct work if standard wiring diagrams supplied are
respected.
WARNING: the modify of parameters could generate incompatibility with supplied wiring diagrams. It is recom-
mended to not modify the original configuration.
Using expansion modules is possible to increase the amount of outputs available in order to do additional checks
and controls (this solution is recommended to avoid the change of work mode of outputs in case of specific ap-
plications).
• The following table shows all the functions that can be assigned to the OUTn programmable digital inputs.
• Each output can be configured so it has a normal or reverse (NOR or REV) function.
• Some functions require another numeric parameter, defined in the index (x) specified by parameter P11.n.02.
• See menu M11 Programmable outputs for more details.
FUNCTION
Disabled
Configurable
Close S.Q1 contactor/
circuit breaker
Open S.Q1 circuit breaker Command to open Q1and eventual springs charging
Close S.Q2 )contactor/
circuit breaker
Open S.Q2 circuit breaker Command to open Q2 and eventual springs charging
Open S.Q/ S.Q2
UVR Coil S.Q1 (line 1)
UVR Coil S.Q2 (line 2)
S.Q1 generator control
S.Q2 generator control
Automatic transfer switch
ready
Global alarm
S.Q1 status
S.Q2 status
Siren
Operating mode
OFF mode
MAN mode
AUT mode
REM(x) remote variable
LIM limits (x)
Dummy load
Load connected to S.Q1
Load connected to S.Q2
Alarms A01-Axx
Alarms UA1..Uax
32
DESCRIPTION
Output disabled
User configuration free
Command to close Q1
Command to close Q2
Open both Q1 and Q2.
It controls the UVR, opening Q1 before the spring load cycle
It controls the UVR, opening Q2 before the spring load cycle
Start /Stop remote control of S.Q1 generator
Start /Stop remote control of S.Q2 generator
Automatic transfer switch in automatic mode, without alarms, ready to switch
Output enabled in the presence of any alarm with the Global alarm propriety enabled
Output energized when there are all conditions to be able to connect the load to the S.Q1
Output energized when there are all conditions to be able to connect the load to theS.Q2
Actives the contact for the external siren
Output energized when the ATS is in one of the modes set with parameter P12.03
Energized when the automatic transfer switch is OFF
Energized when the automatic transfer switch is in MANUAL mode
Energized when the automatic transfer switch is in AUT mode
Output controlled by remote variable REMx (x=1..16)
Output controlled by the state of the limit threshold LIM(x) (x=1..4) defined by the index
parameter
Output enabled when self-test with dummy load is running.
Q1 closed
Q2 closed
Output energized with alarm Axx is enabled (xx=1...alarms number)
Output energized with alarm Uax is enabled (x=1...4)