8.2 System Functions

8.2.1 Monitoring

8.2.2 App View

Issue 06 (2020-05-21)
In the figure, RF_Z indicates wireless networking. RF_Z (1) devices can communicate with the
ECC800-Pro in wireless mode. The RF_Z (2) iBOX and iBAT communicate with each other in
wireless mode. RF_Z (1) and RF_Z (2) devices use different protocols and are isolated from each
other.
After the access actuator, skylight actuator, multi-functional sensor and ECC800-Pro are connected
through PoE and they communicate successfully, wireless communication is automatically set up.
Connect the signal cable from each camera and VCN to the LAN switch in the following scenarios:
(1) Four or more cameras are deployed in a single smart module. (2) The cameras outside the smart
module are connected to the smart module, and there are at least four cameras inside and outside the
smart module. (3) Multiple smart modules share one VCN. (4) There are at least two VCNs.
Temperature and humidity monitoring: Detects and collects statistics on the ambient
temperature and humidity inside the smart module.
Water leakage monitoring: Detects water leakage at the bottom of the smart module and
provides real-time alarm signals.
Smoke monitoring: Detects smoke in the smart module and provides real-time alarm
signals.
Power distribution monitoring:
a.
Detects and collects statistics on the total input phase voltage, current, frequency,
power factor, electric energy, active power, apparent power, load rate, THDv, THDi,
and cabinet interior busbar temperature for the smart module.
b.
Detects the current, electric energy, switch status, contact temperature, and load rate
of the IT and smart cooling product power distribution branches; collects statistics
on electric energy by month or year.
Smart cooling product monitoring:
a.
Monitors the supply and return air temperature and humidity in real time.
b.
Configures the supply air temperature set point in a unified manner, without the
need to separately configure it for each smart cooling product.
c.
Monitors and displays the fan speed, and displays the running percentage.
d.
Displays the cooling load rate.
e.
Monitors and displays the compressor running status.
f.
Provides reminders on regular air filter replacement.
g.
Displays the real-time running status of the heating and humidifying.
Video surveillance: Connects to three cameras and provides PoE power supply; accesses
real-time video images on the WebUI and invokes historical monitoring data.
App view is for reference only.
Generates a 3D layout view that matches the actual layout of the smart module,
including the PDF, smart cooling product, IT cabinet, and temperature and humidity