Certification
6.2 EMC and Environmental Type Tests
IEC 60255-5
EMC Immunity Type Tests per IEEE 1613
Note
The RUGGEDCOM RS900G meets Class 2 requirements for an all-fiber
configuration and Class 1 requirements for copper Ports. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
Fast Transient
Dielectric Strength
Environmental Type Tests
IEC 60255-21-1
IEC 60255-21-2
34
Test
HV Impulse
Description
ESD
Radiated RFI
Oscillatory
HV Impulse
Test
Description
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Description
Vibration
Shock
Test Levels
2 kV
2 kV
5 kV (Fail-Safe
Relay output)
5 kV
5 kV
Test Levels
± 8 kV
± 15 kV
35 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
2.2 kV Common Mode @ 1 MHz
2.5 kV Common and
Differential Mode @ 1 MHz
2.5 kV Common and
Differential Mode @ 1 MHz
5 kV (Failsafe Relay)
5 kV
5 kV
0.5 kV (Failsafe Relay)
2 kV
2 kV
Test Levels
Severity Levels
2g @ 10-150 Hz
Class 2
30g @ 11 ms
Class 2
RUGGEDCOM RS900G
Installation Manual, 01/2021, C79000-G8976-1025-08
Severity
Levels
Need help?
Do you have a question about the SIMATIC NET RUGGEDCOM RS900G and is the answer not in the manual?