Variable address
Description
Number of fan speed used
1 = 1 fan speed is used
11
2 = 2 fan speeds are used
3 = 3 fan speeds are used
Change-over mode (0-3) and fan release function (4-7) via heat pump
supply sensor
0 = Manual setting in display 1 = Manual Heat
2 = Manual Cool
12
3 = Automatic via analog or digital input
4 = manual setting in the display via button 5 = Manual Heat
6 = Manual Cool
7 = Automatic via digital input DI
Temperature difference between the room temperature and the water
13
temperature to switch to heating (P009 = 3) or to release the fan at heat
mode (P009 = 7)
Temperature difference between the room temperature and the water
14
temperature to switch to cooling (P009 = 3) or to release the fan at cool
mode (P009 = 7)
15
Switch on delay for terminal DI
16
Switch off delay for terminal DI
Remote setting of the current controller state 0 = Off
17
1 = No Action 2 = Standby 3 = No Action 4 = Occupied
5 = No remote control
18-29
Not used
Manual or Auto control of output for Heat valve (terminal Heat)
0 = Manual Off
30
1 = Manual On
2 = Auto (output is controlled by the heat demand)
Manual or Auto control of output for Cool valve (terminal Cool)
0 = Manual Off
31
1 = Manual On
2 = Auto (output is controlled by the cool demand)
32-33
Not used
Manual/Auto Fan control, 3-speed
fan 0 = No fan speed active
1 = Fan speed 1 is active on DO FAN1
34
2 = Fan speed 2 is active on DO FAN2
3 = Fan speed 3 is active on DO FAN3
4 = Auto. Fan speed follows heat or cool demand according to the
application.
35-36
Not used
User defined setpoint adjustment (SP adj ) set by using the buttons on
37
the front. Can be reset remotely. 0 = No current setpoint adjustment
made.
Positive user defined setpoint adjustment.
38
The maximum allowed setpoint adjustment (SP adj ) increase.
Negative user defined setpoint adjustment.
39
The maximum allowed setpoint adjustment (SP adj ) decrease.
40-43
Not used
44
Heat valve exercise hour, 0 – 23h
45
Cool valve exercise hour, 0 – 23h
Sensor connected to AI Temp
0 = No sensor connected (Internal room sensor is used) 1
46
= Room temperature sensor
2 = Change-over temperature sensor or fan release function
47
Not used
Contact/detector connected to the terminal DI
0 = No contact connected
48
3 = Presence detector (activate Occupied state) 4
= Change-over contact
49-52
Not used
Display inactive delay
53
Delay for the display to dim down to Idle mode. If
set to 0 the display never dims down.
1-2 = Not used
23
Default
Unit
Scale
value
-
3
1
-
4
1
K
30
10
K
30
10
min
0
1
min
0
1
-
5
1
-
2
1
-
2
1
-
4
1
K
0
10
K
30
10
K
30
10
h
23
1
h
23
1
-
2
1
-
0
1
s
0
30
Min
Max
value
value
1
3
0
7
10
250
10
250
0
120
0
120
0
5
0
2
0
2
0
4
-200
200
0
200
0
200
0
23
0
23
0
2
0
4
0
600