Fill Rate/Min (2.4.2.); Empty Rate/Min (2.4.3.) - Siemens SITRANS LR200 7ML5422 Operating Instructions Manual

Radar transmitter with ma/hart
Table of Contents

Advertisement

7.2.3.2

Fill rate/min (2.4.2.)

Fill rate defines the maximum rate at which the reported sensor value
increase. Allows you to adjust the device's response to increases in the actual material level.
Fill rate is automatically updated whenever Response rate (2.4.1.) (Page 101) is altered.
Note
Enter a value slightly greater than the maximum vessel-filling rate, in units per minute.
Response rate (2.4.1.) (Page 101)
Options
Range
Related
parameter
The value produced by the echo processing which represents the distance from sensor
1)
reference point to the target.
7.2.3.3

Empty rate/min (2.4.3.)

Empty rate defines the maximum rate at which the reported sensor value
increase. Allows you to adjust the device's response to increases in the actual material level.
Empty rate is automatically updated whenever Response rate (2.4.1.) (Page 101) is altered.
Note
Enter a value slightly greater than the maximum vessel-emptying rate, in units per minute.
Response rate (2.4.1.) (Page 101)
Options
Range
Related parameters
The value produced by the echo processing which represents the distance from sensor
1)
reference point to the target.
102
slow (factory setting)
medium
fast
0 to 99999 m / min.
Units (2.2.1.) (Page 99)
slow (factory setting)
medium
fast
0 to 99999 m / min.
Units (2.2.1.) (Page 99)
Fill rate (2.4.2.)
0.1 m/min (0.32 ft/min)
1.0 m/min (3.28 ft/min)
10.0 m/min (32.8 ft/min)
Empty rate
0.1 m/min (0.32 ft/min)
1.0 m/min (3.28 ft/min)
10.0 m/min (32.8 ft/min)
SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE
is allowed to
1)
is allowed to
1)