Level (2.5.3.); Analog Output Scaling (2.6.); Current Output Function (2.6.1.) - Siemens SITRANS LR200 7ML5422 Operating Instructions Manual

Radar transmitter with ma/hart
Table of Contents

Advertisement

7.2.4.3

Level (2.5.3.)

Note
• The default setting depends whether your device is a standard or NAMUR NE 43-
compliant device.
• Material Level (2.5.1.) must be set to VALUE to enable the Level value to be reported.
Allows the user to define the mA value to be reported when the Fail-safe timer expires.
Device type
Values
Factory setting
7.2.5

Analog output scaling (2.6.)

7.2.5.1

Current output function (2.6.1.)

Allows CURRENT OUTPUT FUNCTION (2.6.1.) to be set independently from SENSOR
MODE (2.2.2.). For example, Sensor Mode may be set to Level and Current Output Function
set to Distance.
Options
Level
Space
Distance
Volume
Manual
Current Output Function must be set to Manual before modifying mA OUTPUT VALUE (2.6.6.).
1)
Remember to restore the previous Current Output Function setting after modifying mA Output Val-
ue.
104
STANDARD
3.56 mA to 22.6 mA
22.60 mA
Sensor reference point
High calibration point
100% 20 mA
Space
Reference point
Low Calibration Point
High Calibration Point
sensor reference point
converts a level measurement to a volume output
allows mA OUTPUT VALUE (2.6.6.) to be set to a user-defined value
1)
NAMUR NE43-COMPLIANT
3.56 mA to 22.6 mA
3.58 mA
0% 4 mA
Distance
Level
Low calibration point
Description
measured as a percentage of the difference be-
tween High Calibration Point and Low Calibration
Point
measured as a percentage of Low Calibration Point
Operating Instructions, 05/2019, A5E32337676-AE
SITRANS LR200 with mA/HART