Memory Map - L&T Electrical & Automation 1 Phase DIN Rail Meter User Manual

Table of Contents

Advertisement

MEMORY MAP

Address
Read only Parameters ( Supported by Function Code 4)
Instantaneous Parameters
30001
R Phase Voltage
30003
Y Phase Voltage
30005
B Phase Voltage
30007
R Phase Current
30009
Y Phase Current
30011
B Phase Current
30013
Average Voltage
30015
Average Current
30017
Total Active Power
30019
Total Reactive Power
30021
Total Apparent Power
30023
Total Power Factor
Format: for above addresses 7 to 11, 15 to 23
1st word – (MSW) 0x0000 if value positive
2nd word – value itself, if positive as indicated by 1st word
2's complement of value, if negative as indicated by 1st word
30025
Line Frequency
30027
Cumulative energy – kWh
30029
Previous Day Consumption-kWh
30031
Present Day Consumption-kWh
30033
Previous Week Consumption-kWh
30035
Present Week Consumption-kWh
30037
Previous Month Consumption-kWh
30039
Present Month Consumption-kWh
30041
Current Push to Push Consumption-kWh
30043
Backup Push to Push Consumption-kWh
30045
Present Month MD-kW
30047
Previous Month MD-kW
Parameters
(if no specific format is mentioned, format is HEX)
0xFFFF if value negative
Words
MF
2
0.01
2
0.01
2
0.01
2
0.001
2
0.001
2
0.001
2
0.01
2
0.001
2
0.0001
2
0.0001
2
0.0001
2
0.001
2
0.01
2
0.01
2
0.01
2
0.01
2
0.01
2
0.01
2
0.01
2
0.01
2
0.01
2
0.01
2
0.0001
2
0.0001
Page 4 of 8