FEATURES
Display
Optical
communication
Push button
 LCD display
 Push-to-Push consumption, Daily, Weekly, Monthly consumption.
 Terminal covers to avoid direct contact of the supply terminals along with sealing provision.
 Data transfer through optical communication*.
 Easy mounting on DIN rail with locking.
 Energy recording at current as low as 0.02A.
* Note:
1) Additional "Wi-Fi Module" is available to get data over Wi-Fi (to be purchased separately).
2) Mobile Application is also available for Energy Monitoring for iOS, Android, Windows & Symbian
Operating systems.
3) RS485 Module is available.
TECHNICAL SPECIFICATIONS
Meter Type
Voltage Rating
Current Rating
Starting Current
Accuracy Class
Operating Voltage
Current Display Range
Operating Frequency
Meter Constant
Measurement Category
Standard Compliance
Enclosure
Dimension
Weight
Communication
FEATURES & TECHNICAL SPECIFICATIONS
1P2W Direct Whole current Operated, Direct
Connected, Unidirectional
240 V (Phase to Neutral)
5A (I
), 40A (I
)
basic
max
0.4% I
basic
1.0 (5% to 800% I
)
basic
168V to 288V
0.05A onwards
50Hz ±5%
3200 Imp/kWh
Category III
IEC 62052-11, IEC 62053-21, IP20
Polycarbonate
36mm x 83mm x 66.5mm (
132 grams(Approximate)
Compatible with Wi-Fi & RS485 communication
Terminal sealing provision
Terminal cover
Pulse LED
Terminal sealing provision
)
Tolerances Apply