CONNECTION DIAGRAM
Neutral
Phase
STANDARDS APPLICABLE
 Radiated RF field immunity
 Conducted RF immunity
 Conducted RF emissions
 Radiated RF Emission
 Fast transient burst (2kV)
 Electrostatic Discharge (±15kV)
 Surge Immunity Test ( ±4kV)

INTERFACE DETAILS

The configuration details to communicate with the module are given below.
Standard
RS485 (half duplex)
Baud Rate
Selectable
(19200, 9600,4800, 2400, 1200)
Parity
Selectable ( None,Odd,Even)
RS485 interface uses MODBUS Protocol in RTU mode. Communicating
Protocol
with the meter involves sending commands to the meter for reading
and writing the particular register. The meter can be addressed with
specific user defined meter address (Slave ID) from 1 to 247
Modbus interface
: IEC 61000-4-3
: IEC 61000-4-6
: CISPR 22
: CISPR-22-A
: IEC 61000-4-4
: IEC 61000-4-2
: IEC 61000-4-5