Refrigerants; Electrical Data Table - Carlyle 06CC Application Manual

Compound cooling compressor
Hide thumbs Also See for 06CC:
Table of Contents

Advertisement

1.5 Refrigerants

All 06CC compressors built after 2099J are approved for
R-22, R-404A, R-407A, and R-507 except compressors

1.6 Electrical Data Table

Compressor
Max
Model
kW
HP
06CC016J101
D101
6.25
G101
06CC017J101
D101
6.25
G101
06CC018J101
D101
6.25
G101
06CC124J101
D101
9.18 6.5
G101
06CC125J101
D101
9.18 6.5
G101
06CC228J101
D101
12.8 7.5
G101
06CC337J101
D101
16.5
G101
LEGEND
LRA — Locked Rotor Amps
MCC — Maximum Continuous Current
RLA — Rated Load Amps
TI
— Texas Instruments
NOTES:
1.
RLA (rated load amps) value shown for new high-efficiency mod-
els is MCC ÷ 1.56 = RLA. Use this recommended (and minimum)
Allowable Operating Range
NOMINAL
MAXIMUM
VOLTAGE
VOLTAGE
206/230
575
400 (50 Hz)
200 (50 Hz)
16
COMPRESSOR MOTOR DATA
Electrical Data
Volts
MCC RLA
575
10.8
5
208/230
27.0
17.3
460
13.5
575
10.8
5
208/230
27.0
17.3
460
13.5
575
10.8
5
208/230
27.0
17.3
460
13.5
575
13.2
208/230
33.0
21.2
460
16.5
10.6
575
13.2
208/230
33.0
21.2
460
16.5
10.6
575
16.7
10.2
208/230
41.6
26.7
460
20.9
13.4
575
18.8
12.1
10
208/230
46.5
29.8
460
23.3
14.9
MINIMUM
VOLTAGE
254
187
661
518
460
342
230
180
in the 16 to 37 cfm range. Compressors in this size range
cannot be used with R-404A, R-407A and R-507 prior to
serial number 2099J- - - - without installing a retrofit com-
pressor valve plate (part number 06CY660-002) kit.
Motor Winding
Resistance
LRA
(Ohms)
6.9
40
3.3
100
0.54
8.7
50
2.1
6.9
40
3.3
100
0.54
8.7
50
2.3
6.9
40
3.3
100
0.54
8.7
50
2.1
8.5
64
2.6
160
0.42
80
1.7
8.5
64
2.6
160
0.42
80
1.7
79
2.0
198
0.31
99
1.3
91
1.7
228
0.26
114
1.0
RLA value to determine nameplate stamping, minimum contactor
sizing and wire sizing.
2.
Compressor operating amps at any specific condition can only be
determined from a performance curve.
3.
RLA values for 06D compressor protected by calibrated circuit
breaker will depend must-trip value of circuit breaker.
4.
Ohm values shown for resistance are approximate and shown for
reference only. Motors from different vendors and motors of differ-
ent efficiencies can differ up to 15% from data shown.
Overload Carlyle
Part No.
Part No.
T.I. No.
HN69GZ032
8347A23-42
HN69GZ024
8347A23-63
HN69GZ014
8347A23-53
HN69GZ032
8347A23-42
HN69GZ024
8347A23-63
HN69GZ014
8347A23-53
HN69GZ032
8347A23-42
HN69GZ024
8347A23-63
HN69GZ014
8347A23-53
HN69GZ037
8347A23-40
HN69GZ214
8348A23-9
HN69GZ038
8347A23-18
HN69GZ037
8347A23-40
HN69GZ214
8348A23-9
HN69GZ038
8347A23-18
HN69GZ004
8347A23-19
HN69GZ306
8347B23-13
HN69GZ010
8347A23-29
HN69GZ025
8347A23-31
HN69GZ309
8347B23-11
HN69GZ024
8347A23-63

Advertisement

Table of Contents
loading

Table of Contents