Start Up-Basic Controls (Plc); Prestart - BeaconMedaes VerusLab 4107 9021 88 Installation, Operation And Maintenance Instructions

Lubricated rotary vane laboratory vacuum system
Table of Contents

Advertisement

Lubricated Rotary Vane Laboratory Vacuum Systems
3B.0
Start-Up - Basic Controls (PLC)
NOTE:
This section is only applicable to Lubricated
Rotary Vane Laboratory Vacuum Systems
with the Basic control system.
3B.1 Prestart-up
The contractor should notify BeaconMedæs
two weeks prior to start-up date to schedule
an appointment for an authorized technician to
review the installation prior to start-up.
CAUTION:
Failure to install the unit properly and
have
an
authorized
BeaconMedæs start-up the system can void
the manufacturer's warranties.
Prestart-up and start-up procedures should be
performed for a new installation or when major
maintenance has been performed.
WARNING:
Have more than one person on hand during
prestart-up and start-up procedures to
ensure safety and to facilitate certain checks.
The main power source to the control panel
should be OFF for the duration of the visual
inspection.
Ensure that the equipment is installed on a
solid level surface. Walk around the system
to ensure that there is enough clearance
on all sides to perform operational checks/
actions and maintenance. The temperature
of the area containing the modules should be
approximately 70°F (21.1°C) with a minimum
ambient temperature of 40°F (4.4°C) and a
maximum ambient temperature of 105°F (40°C).
4107 9021 88.01
technician
from
3B-1
Check the intake piping for proper size and
connection.
Check all piping system joints that might have
come loose during shipment and installation
to ensure they are tight.
Check the air receiver, controls, and pumps
for damage.
Check the drain valve on the air receiver.
Check all valves for full open and full close
travel. Ensure that the system's valves are
positioned for proper operation. (Refer to
labeling on valve handles).
Remove all packing material from the unit.
Check the electrical connections to the
control cabinet.
Verify electrical service. Before starting the
system, check to see that voltage, amperage,
and wire size are appropriate.
CAUTION:
Electrical service must be as specified or
damage to equipment may occur.
WARNING:
To prevent electrical shock, ensure that ALL
electrical power to the system is OFF, including
the disconnect switches and Automatic-Off
-Manual touch screens on the control panel.
The facility's supply circuit breaker should
also be locked out.
Open the electrical cabinet by loosening the
latch and disconnect switches on the front.
CAUTION:
Vibration during shipment and installation
can loosen electrical terminals, fuse inserts,
and mechanical connections. Tighten as
necessary.

Advertisement

Table of Contents
loading

Table of Contents