Intake Piping - BeaconMedaes VerusLab 4107 9021 88 Installation, Operation And Maintenance Instructions

Lubricated rotary vane laboratory vacuum system
Table of Contents

Advertisement

Check all electrical connections within the
vacuum system that may have loosened during
shipment.
Qualifi ed electricians only should make power
connections to the control panel and any
interconnecting
wiring.
has openings for electrical and alarm/data
connections. Do not drill additional holes in
the control panel as this may void the system
warranty. See Figure 2.1 for opening locations.
Alarm Wires
Data
Connection
Figure 2.1 Electrical / Alarm / Data Openings
WARNING:
Before operating the pump, be sure to check
the motor rotation. Damage can result from
running the pump backwards.
When viewing the motor from the motor
fan housing end, the rotation should be
counterclockwise. If the motor is clockwise,
Lubricated Rotary Vane Laboratory Vacuum Systems
The
control
panel
Electrical
Connection
NOTE:
It may be necessary to switch two of the
leads when performing start-up, if the
pump rotation is in the wrong direction.
isolate power to the panel and reverse the
rotation by switching two of the leads.
Ensure that the emergency generation system
electrical supply is consistent with the vacuum
system's requirements.
The electrical controls for the system were wired
at the factory and were fully tested.
Three-phase power supplied from emergency
generator(s) must match that of the normal
supply to allow for correct direction of the motor
rotation at all times.
2.6

Intake Piping

Before connecting any piping, the plastic thread
protector installed in the connection port must be
removed. We recommend that the main vacuum
line to the receiver should not be reduced below
that provided on the receiver. Smaller lines will
result in lower pumping speeds than the rated
values. Long piping runs may need to be increased
in size to minimize pressure drop. Improper line
sizing may result in a loss of capacity. Ideally,
piping should be constructed using long radius
elbows and a minimum number of turns to keep
piping as short as possible to minimize pressure
drop between the system and end point of use.
All secondary lines should be taken from the
top or side of the main line to prevent any
WARNING:
Do
not
allow
explosive gases, liquids or solids to enter the
pump.
2-3
aggressive,
corrosive
4107 9021 88.01
or

Advertisement

Table of Contents
loading

Table of Contents