4 zones gas detection central unit with rs232 serial output

Advertisement

Quick Links

x
230V~ power supply
x
Controls up to 4 zones
x
Manages CO, L.P.G. and Methane (CH
x
Wide parameters configuration freedom
x
Last alarm conditions data retention
x
LCD backlight 2 x 16 characters display
x
9 modules DIN rail mount
x
RS232 serial output
This is a microcontroller based device capable of monitoring the
gas concentration in up to 4 different zones: for each of these a
4 .. 20 mA transmitter can be wired for measurement and
detection of either L.P.G., Methane or Carbon Monoxide (CO).
Ã
After power-up the display shows the following information:
Ã
ÃÃÃÃÃÃÃÃÃÃÃÃà “‚rÃ
ÃÃÃÃÃÃÃÃÃÃÃÃÃ ADSHX6S@)ÃÃÃÃÃÃÃ Ã
ÃÃÃÃÃÃÃÃÃÃÃÃà W@STDPIÃÃÁ Ã
ÃÃÃÃÃÃÃÃÃÃÃÃÃ
ÃÃÃÃÃÃÃÃÃÃÃÃà “‚rÃ"
where ' nnnnnn ' is the firmware version installed in the device.
This information will remain visible for about 2 seconds. After this
time the main information will be displayed (example):
ÃÃÃÃÃÃÃÃÃÃÃÃà “‚rÃ
ÃÃÃÃÃÃÃÃÃÃÃÃÃ B)ÃÃÈfÃÃ8)Ã$ƒf Ã
ÃÃÃÃÃÃÃÃÃÃÃÃÃ B)Ã "ÈQÃÃH)Ã$È6 Ã
ÃÃÃÃÃÃÃÃÃÃÃÃÃ
ÃÃÃÃÃÃÃÃÃÃÃÃà “‚rÃ"
Each zone provides the following information:
The first letter from left explains the transmitter type wired to the
central unit.
The transmitters which can be wired to the central unit can be
different for each zone; the detectable gases are the following:
- L.P.G.:
- Methane (CH
):
4
- Carbon Monoxide:
Values displayed on the right, in % L.E.L. (in case L.P.G. or
Methane transmitters are connected) or ppm (in case of Carbon
Monoxide) are the actual gas concentration values measured by
the transmitters. The last letter shown on the display for each zone
indicates the actual state of the relevant transmitter as explained
in the following:
f
: Active state (measuring, normal operation).
'
B
: Fault on the '
'as transmitter (Iout=2 mA).
'
B
A
: '
'ault over the current loop (either short or open circuit
'
A
between any of the sensor wires: Iout=0 mA ).
Q
: '
'realarm state.
'
Q
6
: '
'larm state. When '
'
6
concentration value, this means that the upper limit of the
measuring range has been exceeded. The '
corresponds to an input current value above 20mA.
The central unit can manage separately the pre-alarm and alarm
conditions through two distinct, Normally Open, output relays.
In case the prealarm threshold is reached, the central unit enables
the relevant relay, which, in turn, closes its output contacts.
In case the alarm threshold state is reached the unit will also
enable the alarm relay thus closing the relevant output contact. At
the same time the central unit has stored the pre-alarm state first
and the alarm state later: the date and hour when the last has
happened will be retained in the central unit memory.
) transmitters
4
“‚rÃ! Ã
“‚rÃ#
“‚rÃ! Ã
“‚rÃ#
display shows letter '
'
B
display shows letter '
'
H
display shows letter '
'.
8
PWS
' is shown in place of the
PWS
In case the gas concentration returns below the pre-alarm
threshold, the relevant relay will return to its normal operation
state or not, according to how the prealarm relay operating mode
Ã
was set in the configuration.
For compliance with the current performance standards the
I‚‡r)Ã
Alarm relay has always a latched operation and this mode cannot
be modified by the user. Whenever either an Alarm situation ('A')
or an Overrange ('OVR') situation is reached, this relay is kept
energised together with the internal buzzer and the red led until
the user intentionally presses for 3 seconds the '
The central unit features one additional relay with changeover
contacts (SPDT) which can be activated according to events and
operating modes set by the installer through the relevant menu.
Ã
The central unit can retain the date and hour of the last alarm
event happened in each zone.
These information can be read by the user at any time by pressing
for 3 seconds the '
pressing '<' or '>' keys to cycle through the zones.
The central unit is normally powered with 230V~ mains voltage.
At terminals 6 and 7 the user can wire a battery backup system
whose purpose is to grant full functionality to the central unit even
in case of power failure (see section [m] for details).
Normally Closed (NC) output of the auxiliary relay is available at
terminals 15 and 16, while the Normally Open (NO) one is
available at terminals 16 and 17.
This output can be used either for driving 'general purpose' loads
as a siren or an flashing light or, with proper configuration of the
relevant parameters, to drive a gas shut-off electrovalve.
Moreover this central unit features two single pole relay contacts
for each zone, one for prealarm and one for alarm.
The number of transmitters which can be wired to the central unit
is 4, each compliant with the 4..20 mA current loop system.
In order to make electrical wirings please refer to the suggested
wiring diagrams. Please also note that all the relay outputs of the
central unit do not feed power to the loads.
In other words all outputs are 'voltage free', giving the user more
freedom to use loads with several operating voltages.
Uuv†Ã8r‡…hyÃVv‡Ãv†ÃIPUÃhƒƒ…‚‰rqÃs‚…Ãv†‡hyyh‡v‚ÃvÃ6U@YÃ
pyh††vsvrqÓ‚r†
à 6yyà v…vt†Ã v‡uà …r€‚‡rà †r†‚…†Ã €ˆ†‡Ã irà €hqrà ˆ†vtà v…r†Ã
à v‡uÃ
$à €€ðà €vv€ˆ€Ã p…‚††Ã †rp‡v‚Ã hqà ‚à y‚tr…à ‡uhÃÃÃ
à !$ÀÃ9‚Á‚‡Ãˆ†rÆh€rÃqˆp‡Ãs‚…ÆvthyÐv…r†ÃhqÀhv†Ã
' state
à DÃ ph†rà ‚sà v†‡hyyh‡v‚Ã ur…rà †‡…‚tà @H8à qv†‡ˆ…ihpr†Ã h…rÃ
ƒ…r†r‡à v‡Ã v†Ã uvtuy’à †ˆttr†‡rqà ‡urà ˆ†rà ‚sà †uvryqrqà phiyr†Ã
Uurà †uvryqà €ˆ†‡Ã irà p‚rp‡rqà ‡‚à ‡urà Bqà ‡r…€vhyà ‚sà ‡urÃ
…ryr‰h‡Ã“‚rÇurÃ8r‡…hyÃVv‡Ã†vqry’Ã
UurÃhƒƒyvhprÀˆ†‡ÃirÐv…rqÇ‚ÇurÃryrp‡…vpÀhv†Ã‡u…‚ˆtuÃhÃ
à † v‡puà phƒhiyrà ‚sà qv†p‚rp‡vtà hyyà ƒ‚yr†Ã vÃ p‚€ƒyvhprÃ
à  v‡uà ‡urà pˆ……r‡Ã †hsr‡’à †‡hqh…q†Ã hqà v‡uà hà p‚‡hp‡Ã
à † rƒh…h‡v‚Ã‚sÃh‡Ãyrh†‡Ã"À€ÃvÃhyyÂyr†Ã
D†‡hyyh‡v‚Ã hqà ryrp‡…vphyà v…vt†Ã ‚sà ‡uv†Ã hƒƒyvhprà €ˆ†‡Ã irÃ
à € hqrà i’à „ˆhyvsvrqà ‡rpuvpvh†Ã hqà vÃ p‚€ƒyvhprà v‡uà ‡urÃ
à p ˆ……r‡Ã‡rpuvphyÃhqÆhsr‡’Ƈhqh…q†Ã
7rs‚…rÐv…vtÇurÃhƒƒyvhprÃirƈ…rǂLj…Ã‡urÀhv†Ãƒ‚r…Ã
1
' key when in main display screen, then
…r†r‡
Ã
' key.
…r†r‡Ã

Advertisement

loading
Need help?

Need help?

Do you have a question about the RGY S00 MBP4 and is the answer not in the manual?

Questions and answers

Summary of Contents for Seitron RGY S00 MBP4

  • Page 1 230V~ power supply Controls up to 4 zones Manages CO, L.P.G. and Methane (CH ) transmitters Wide parameters configuration freedom Last alarm conditions data retention LCD backlight 2 x 16 characters display 9 modules DIN rail mount à RS232 serial output In case the gas concentration returns below the pre-alarm threshold, the relevant relay will return to its normal operation state or not, according to how the prealarm relay operating mode...
  • Page 2 à ‚ ss press ’enter’ D‡Ã v†Ã ˆƒÃ ‡‚à ‡urà v†‡hyyr…à u‚†rà …r†ƒ‚†vivyv‡’à v†Ã ‡‚à †r‡ˆƒÃ hà xà qr‡rp‡v‚Ã †’†‡r€Ã vÃ p‚€ƒyvhprà v‡uà ‡urà r‘v†‡vtà Ãà †‡hqh…q†à i‚‡uà @ˆ…‚ƒrhÃ hqà Ih‡v‚hyà ‡‚à pu‚‚†rà ‡urà a‚r Àhhtr€r‡ à à Pressing ’<’ or ’>’ cycles …†‡ÃÃ13ÃÃÃÃÃÃr‡...
  • Page 3 press ’enter’, then ’>’ 5 times a‚r Àhhtr€r‡ à …†‡ÃÃ13ÃÃÃÃÃÃr‡ à à à a‚r Ã…À‚qr)ÃP à à Pressing ’+’ or ’-’ cycles …†‡ÃÃ13ÃÃÃÃr‡ à à between ’O’ and ’L’ Ãà press ’enter’, then ’>’ twice : Pre-alarm relay is non-latched. xÃ...
  • Page 4 the unit detects a concentration level above the alarm threshold operated: from this moment on the unit will retain the correct date or in case of a fault detected on any zone. and time even in case of power lack, thanks to the internal real time clock and backup battery (allow 24h of charging time in case Ã...
  • Page 5 Check and repair the current loop line regarding the faulty zone. “‚rà “‚rÃ! à Ãà 01. This device can be set either for flammable gases like Hr††htrÃqv†ƒyh’rq) H)BÃÃÃÃÃÃÃÃà à Methane (’M’) and LPG (’G’) or for toxic gases like CO (’C’). 02.
  • Page 6 à Pre-alarm relays action could be ’auto-resetting’ in case the xà latching parameter (under Zone management - Zone pre-alarm mode) has been set to ’O’ (open). Please refer to proper section for further details. Auxiliary relay action could be ’auto-resetting’ in case the xÃ...
  • Page 7 Ã ƒ)Ã Alarm value + meas. unit (p=ppm, %=%L.E.L.). Ã Alarm relay mode ( L= locked, O = open). Ã 18S3)Ã CR character (Carriage Return = 0Dhex or 13dec). Ã 1GA3)Ã This Central Unit features a standard RS-232 output whose LF character (Line Feed = 0Ahex or 10dec).
  • Page 8 à AvtÃ$à Fr’i‚h…qÃr‘ƒyhh‡v‚Ã à Inside the central unit a buzzer is mounted which is activated any time an abnormal situation is detected. à 7ˆ““r…à This key features two functions: !à Sr†r‡Ãiˆ‡‡‚à Quits the current menu and returns to the upper level menu. Ã...
  • Page 9 + V I n Gnd Pr1 Al1 Pr2 Al2 Pr3 Al3 Pr4 Al4 Aux RL RS-232 ACC SGB 12 RGY S00 MBP4 + V I n Gnd + V In Gnd NO NO           &...
  • Page 10 + V In Gnd Pr1 Al1 Pr2 Al2 Pr3 Al3 Pr4 Al4 Aux RL RS-232 ACC SGB 12 RGY S00 MBP4 + V In Gnd + V I n Gnd NO NO           &...
  • Page 11 + V In Gnd Pr1 Al1 Pr2 Al2 Pr3 Al3 Pr4 Al4 Aux RL RS-232 ACC SGB 12 RGY S00 MBP4 + V In Gnd + V I n Gnd NO NO           &...
  • Page 12 + V I n Gnd Pr1 Al1 Pr2 Al2 Pr3 Al3 Pr4 Al4 Aux RL RS-232 ACC SGB 12 RGY S00 MBP4 + V I n Gnd + V In Gnd NO NO           &...