Siemens QSA2700D Basic Documentation page 21

Fine dust room sensor
Hide thumbs Also See for QSA2700D:
Table of Contents

Advertisement

6.3 Troubleshooting
6.4 Disposal
Siemens
Error
QSA2700D
QSA2700D
QSA2700D
QSA2700
Red permanently on
QSA2700
Red flashing (0.5 s on /
0.5 s off)
QSA2700
Red / yellow flashing (0.5
s red / 0.5 s yellow)
The device is considered electrical and electronic equipment for disposal in terms of
the applicable European Directive and may not be disposed of as domestic garbage.
Dispose of the device through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Description
0-10 V output
Replace sensor module
Present 0 V (2
when:
s) and 10 V (2
s) one by one in
1.
it is broken;
turn
2.
it reaches its
lifetime.
Check for:
Present 0 V (5
s) and 10 V(2 s)
1.
the communication
one by one in
error between
turn
sensor module and
product MCU;
2.
missing sensor
module.
Warning of possible
Present the
inaccurate
measured value
measurement
Error 1, replace sensor
Present 0 V (2
module
s) and 10 V (2
s) one by one in
turn
Error 2, communication
Present 0 V (5
error
s) and 10 V (2
s) one by one in
turn
Warning of possible
Present the
inaccurate
measured value
measurement
Maintenance
6
Troubleshooting
Modbus
Value of register
260 changes
from 0 to 1
Value of register
260 changes
from 0 to 2
Value of register
260 remains 0
without change
Value of register
260 changes
from 0 to 1
Value of register
260 changes
from 0 to 2
Value of register
260 remains 0
without change
21 | 26