Oil burner controls
Hide thumbs Also See for LAL Series:

Advertisement

Function (cont´d)
Flame supervision
Preconditions for
burner startup
With the exception of LAL1...
Startup sequence
A
Start command by «R»
 «R» closes the start control loop between terminals 4 and 5
The sequence switch starts to run
-
- Only prepurging, fan motor at terminal 6 receives power
- Pre- and postpurging, fan motor or flue gas fan at terminal 7 receives power on completion of «t7»
-
On completion of «t16», the control command for opening the air damper is delivered via terminal 9
-
Terminal 8 receives no power during the positioning time
The sequence switch continues to run only after the air damper has fully closed
-
t1
Prepurge time with air damper fully open
-
The correct functioning of the flame supervision circuit is checked during «t1»
-
The burner control will initiate lockout if correct functioning is not ensured
With LAL2... / LAL3...:
Shortly after the beginning of «t1», the air pressure switch must change over from terminal 13 to terminal 14
 otherwise, the burner control will initiate lockout
 start of the air pressure check
t3
Short preignition time
«Z» must be connected to terminal 16, release of fuel via terminal 18.
t3´
Long preignition time
«Z» connected to terminal 15.
With LAL1...
«Z» is switched on when start command is given.
With LAL2... / LAL3...
«Z» is switched on when «LP» changes over.
 no later than at the end of «t10»
On completion of «t1», the LAL... drives the air damper to the low-fire position via terminal 10
-
 the low-fire position is defined by the changeover point of auxiliary switch «m» in the actuator
-
During the positioning time, the sequence switch maintains its position
 until terminal 8 receives power via «m»
The motor of the sequence switch is switched to the control section of the LAL...
-
 positioning signals delivered to terminals 8 now have no impact on the further startup sequence and
on subsequent burner operation
10/19
Building Technologies Division
Infrastructure & Cities Sector
Flame detector and flame simulation test are made automatically during burner off
-
times and the prepurge time «t1»
-
If loss of flame occurs during operation, the burner control will initiate lockout
If automatic repetition of the startup sequence is required, the clearly marked wire
-
link on the plug-in section of the LAL... must be cut away  start repetition
-
Burner control is not in the lockout position
-
Sequence switch is in its start position
 with LAL1..., voltage is present at terminals 4 and 11
 with LAL2... / LAL3..., voltage is present at terminals 11 and 12
Air damper is closed
-
End switch «z» for the «CLOSED» position must feed power from terminal 11 to
-
terminal 8
-
Contact of the limit thermostat or pressure switch «W» and the contacts of any
other switching devices in the control loop between terminals 4 and 5 must be
closed  e.g. a control contact for the oil preheaters temperature
Normally closed contact of the air pressure switch must be closed  «LP» test
-
CC1N7153en