Technical Data - Riello G3R Installation, Use And Maintenance Instructions

Light oil burner
Table of Contents

Advertisement

Available languages

Available languages

TECHNICAL DATA

TYPE
Output - Thermal power
Fuel
Electrical supply
Motor
Capacitor
Ignition transformer
Pump
Absorbed electrical power
Burner with CE marking in conformity with EEC Directives: Electromagnetic Compatibility 2004/108/EC,
Low Voltage 2006/95/EC, Machines 2006/42/EC and Efficiency 92/42/EEC.
The burner meets protection level of IP 40, EN 60529.
CE Certification No.: 0036 0315/01 as 92/42/EEC.
8
4
3
1 – Return line
2 – Suction line
3 – Gauge connection
4 – Pump pressure regulator
5 – Vacuum gauge connection
6 – Screws fixing air damper
7 – Hydraulic jack with air damper
8 – Lock-out lamp and reset button
9 – Flange with insulating gasket
2666
2  3 kg/h - 23.8  35.5 kW
(H
i
Gas oil, viscosity 4 –6 mm
Single phase, 230 V ± 10%
Run current 0.7 A – 2850 rpm – 298 rad/s
Secondary 8 kV – 16 mA
Pressure: 8 – 15 bar
Fig. 1
7
6
6
9
D6252
HYDRAULIC JACK OPERATION 7)(Fig. 1)
It is strongly recommended a periodic check of
the pump pressure operation (annually or better
every six months, if the burner operation is con-
DANGER
tinuous).
If the value is lower than 1 bar, compared to that
one of the initial setting, please check the clean-
ing of the pump and line filters.
In case the pressure setting was not restorable,
please replace the pump, in order to guarantee
that the pump pressure during the pre-purge time
is at least 3.7 bar.
1
GB
510 T3R
= 11.86 kWh/kg)
2
/s at 20°C
~
50Hz
4 F
0.165 kW
2
ENGLISH
1
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

510 t3r

Table of Contents