INSTALLATION INSTRUCTIONS AND OWNER'S HANDBOOK CAUTION: All gas burners MUST be installed by trained and licensed technicians. WARNING: Installation of this burner must conform with local codes or, in the absence of local codes, with the Standard for the Installation of Domestic Gas Conversion Burners, ANSI Z21.8-1984, and Addendum, Z21.8a-1989, and the National Fuel Gas code, ANSI Z223.1-1984, and CAN/CGA B149.1 &.2.
" NPT plugged tapping must be installed immediately upstream of the burner gas train supply connection and must be accessible for a test gauge. d) If required by local codes, provide gas vent lines at the gas regulators and valve (Riello gas trains are equipped with vent limiting diaphragms).
SERIAL NUMBER IDENTIFICATION Your Riello burner may have been manufactured in more than one location and therefore there are two possible serial number identification. The Riello 9 character serial number, example, (06) (01) (12345) 06 01 12345, is identified as follows: = Last two digits of the year of manufacture;...
7 1 / 2 ” - 190 mm 8 15 / 32 ” - 215 mm D7351 Model G400 inches NOTE: Actual available insertion length must be measured from tip of end cone to face of mounting gasket. ELECTRODE AND FLAME PROBE ADJUSTMENTS...
This gas train scope of supply meets the minimum controls requirements according to CSA Canada and USA regulations. Any additional requirements needed to meet local codes are the responsibility of others. FIELD SUPPLIED RIELLO SUPPLIED D7343 VALVE LEGEND 1 - Gas supply & flow direction of gas...
4) Check that you have adequate space for servicing the equipment. The Riello burner requires a minimum of 13 inches clear space behind the red cover. This is required to allow easy removal of the cover for servicing and periodic maintenance.
INSTALLATION OF SEDIMENT TRAP AND BURNER SUPPLY Gas piping to the burner must be -inch minimum. Install only a full-ported shutoff valve. The valve must be located outside the appliance jacket, and the pressure gauge port must be accessible. PRESSURE TEST-OVER PSIG.
FACTORY WIRING DIAGRAM NOTE: The SAFETY SWITCH on the 525SE CONTROL BOX is equipped with a contact allowing remote sensing of burner lockout. The electrical connection is located on the CONTROL BOX ter- minal 4 as indicated. Should burner lockout occur, the 525SE CONTROL BOX will supply a power source of 120 Vac to the connection terminal.
SETTING UP THE BURNER After burner output has been determined, use TABLE 1 below AS AN INITIAL GUIDE for burner settings. All settings in this table were obtained under the following conditions. 0 (zero) draft in the combustion zone; Standard lab test boiler; ...
c) Repeat step (a), making adjustments to the gas valve, until flame is established. d) Once flame has been established, set your manifold pressure to the desired value from TABLE 1. 4) Check combustion gases using proper combustion analysis equipment to ensure safe levels of CO and CO dur- ing appliance heat up.
AIR GATE ADJUSTMENT To regulate the combustion air, adjust the manual air gate (3), by loos- ening the locking screws (4). Once the optimal adjustment is reached, tighten the locking screws (4). EXAMPLE SETTING - (for natural gas) To set the air intake for a desired burner output of 243,600 Btu/hr, use TABLE 1 to determine the correct air gate setting.
DIAPHRAGM INSTALLATION AND COMBUSTION HEAD SETTING A proper diaphragm (C) has to be installed in the combustion head gas line, according to TABLE 1. A complete set of gas diaphragms is delivered with the burner packaging as equipment. The burner leaves the factory with the C6 diaphragm already installed.
PRESSURE WORKING CHART The chart below shows effects of pressure in the combustion zone on the minimum/maximum burner outputs. In this example, with a maximum operating pressure of 0.6 inches water column in the combustion zone, you will be able to obtain a maximum of 370,000 Btu/h burner output.
COMBUSTION CHECKS It is advisable not to exceed a measured reading of 10% CO for Natural Gas or 12% CO for Propane Gas. For safety reasons, the value of .02% (200ppm) free air sample must not be exceeded. IONIZATION CURRENT Red wire connect The minimum amount of current necessary for the control box to operate properly is 3 micro Amps DC.
7) Do a complete combustion test with the burner cover in place and the air gate locking screws secure. Your Riello 40 gas burner is only part of your heating system. Once every year you should have your heating appliance serviced by a qual- ified service technician.
PROPANE BURNER APPLICATION The burner leaves the factory to run on Fig. A natural gas. It is available a kit, on request, that allows the burner to run on propane. D7346 TECHNICAL FEATURES The thermal output and operating range of burners converted to use propane are the same as for burners running on natural gas.
Page 20
SETTING UP THE BURNER After burner output has been determined, use TABLE below AS AN INITIAL GUIDE for burner settings. All settings in this table were obtained under the following conditions. 0 (zero) draft in the combustion zone; Standard lab test boiler; ...
SPARE PARTS LIST CODE DESCRIPTION 3007234 Burner back cover 3020321 Air pressure switch 3001162 Primary control box 525 SE/A 3002307 Primary control sub-base 3007342 C7020226 120/24 Volt transformer 3007288 Air switch tube and connector 3007310 Ionization lead 3007293 Air tube cover plate 3006688 Chassis mounting collar 3007448...
Page 23
CODE DESCRIPTION 3005447 Gas test point 3000870 Hinge assembly 3020229 Drawer assembly diaphragm ACCESSORIES AND GAS TRAIN C7010003 Mounting bracket transformer Honeywell VR8305M4009 solenoid 2903334...
BURNER START UP REPORT Model number: Serial number: Project name: Start-up date: Installing contractor: Phone number: Model number: Serial number: Project name: Start-up date: Installing contractor: Phone number: GAS OPERATION : Low Fire Gas Supply Pressure: High Fire : Low Fire Main Power Supply: High Fire Control Power Supply:...
Page 28
RIELLO S.p.A. I-37045 Legnago (VR) Tel.: +39.0442.630111 http:// www.riello.com RIELLO BURNERS NORTH AMERICA http://www.riello.ca 35 Pond Park Road 2165 Meadowpine Blvd Hingham, Massachusetts, Mississauga, Ontario U.S.A. 02043 1-800-4-RIELLO Canada L5N 6H6 Subject to modifications...