4.2 Auto Acknowledge : User can choose auto acknowledge function if required ,
afterward select a delay time that can be set between 1-240 seconds.
4.3 Lamp Flashing Rate : The flashing rate can be specified or choosen from the flash
timing of configuration window. The range of flashing rate starting from 125ms to
1000ms ( 125 ms. per step ).
4.4 Modbus Setting
module as required.
4.5 Input Time Delay
0.6 , 0.8 , 1.0 , 1.2 , 1.4 , 1.6 , 1.8 , 2.0 , 2.2 , 2.4 Sec.
4.6 Input Indicator
4.7 Alarm Control Type : User can choose fault input type which shall be dry contact
only such as NO (Normally Open) or NC (Normally Close) contact.
ESPAN04 Series – User Manual
: User can choose address or change address of the master
: User can choose input time delay which start from 0.2 , 0.4 ,
: User can select indicator function in case of some requirement
- 11 -
@ESPAN
www.esptechno.com