PIR detector switch
7. SETTINGS
- Parameters:
Sensor parameters
Time delay
Sensitivity
Daylight setpoint
Auto on/Auto off
Walkthrough
Manual on/Auto off
Initial
Maintain
Retrigger
Calibration
Light regulation
Provision of light
Time delay: Time for which light is switched on following detection.
Sensitivity: Detector range setting.
Daylight setpoint: Brightness value below which the light is switched on and
above which the light is switched off.
Auto on/Auto off mode:
The light is switched on automatically:
- when presence is detected, if the natural brightness is too low.
The light is switched off automatically:
- Where no presence is detected and at the end of the time delay set.
- Or if there is a sufficient level of natural light (activated setting).
Any new detection causes an automatic switch on if there is insufficient light.
Walkthrough:
- If there is no presence detected in the 3 minutes following an initial detection, the
product will cut off after 3 minutes.
- If a new presence is detected in the 3 minutes following the initial detection,
the device will cut off at the end of the time delay set.
Manual on/Auto off mode:
Comes on via a manual switch, automatic switch off:
- Where no presence is detected and at the end of the time delay set..
Following switch off, any new detection within a 30-second period will cause the
device to be switched on automatically.
After 30 seconds the device is switched on via a manual switch.
Initial detection: Light switched on from first detection.
Maintain: The load remains active if any new presence is detected.
Retrigger: Function allowing automatic start of the product at the end of 30
seconds following the load being switched off.
Upon switch off, any new detection within a 30-second period will cause the device
to be switched on automatically.
After 30 seconds the device must be switched on manually.
Calibration: The surrounding level of light measured with a luxmeter will then
have to be transmitted to the detector.
Light regulation : Light switched off automatically 10 minutes after the Daylight
setpoint has been exceeded. If the light level is below the Daylight setpoint, the
light is activated automatically after 20 seconds.
Provision of light: quantity of additional lux provided when the light is switched
on.
Technical data sheet: F01031EN/02
CONTENTS
Default value
Modifiable parameters
3,5,10,15,20 min
5s
0 - 59 min 59s
PIR (very high)
Low, medium, high, very high
20, 100, 300, 500, 1000 lux
1000 lux
0 - 1275 lux
Inactive
Enabled/Disabled
Active
Enabled/Disabled
Inactive
Enabled/Disabled
PIR
Non modifiable
PIR
Non modifiable
PIR
PIR / Disabled
0 - 99995 lux
Active
Enabled/Disabled
Auto
Auto - 1275 lux
Updated: 17/08/2010
Catalogue number(s): 488 01
Configuration tools
88230
88235
- Modifying parameters using configuration tools
• 882 35: Simplified configuration tool
• 882 30: advanced configuration tool
When the detector receives an PIR command from a configuration tool,
the green indicator flashes acknowledging the modification.
Note: Using configuration tools deselects the initial potentiometer
settings.
- Return to settings using potentiometer (or the factory settings):
First press: press LEARN briefly, the LED blinks slowly.
Second press: Keep LEARN pressed down for 10 seconds until the
LED blinks rapidly.
Created: 22/02/2010
Parameters can be modified
manually
By potentiometer: 5s - 30min
By potentiometer: 1 - 1000 lux
By auto/eco switch
By auto/eco switch
3/4