Modello 15 - 43
L
N
PE
L = linea / line
LINEA ALIMENTAZIONE: PREDISPORRE A MONTE UNA ADEGUATA PROTEZIONE CON INTERRUTTORE MAGNETOTERMICO DIFFERENZIALE
N = neutro / neutral
POWER LINE: PROVIDE A PROPER SAFETY DEVICES EQUIPPED WITH DIFFERENTIAL MAGNETOTHERMAL SWITCH
PE = terra / protective earth
PARAMETRI DEL CONTROLLORE DA MODIFICARE RISPETTO ALLE IMPOSTAZIONI DI DEFAULT (CONSULTARE ANCHE IL MANUALE ISTRUZIONI DEL TERMOSTATO
CONTROL PANEL PARAMETERS TO BE MODIFIED WITH RESPECT TO THE DEFAULT SETTING
P01 = 0
P03 = 3
P23 = 0
P24 = 99
It
A TRATTEGGIO SONO RAPPRESENTATI I COLLEGAMENTI DA EFFETTUARSI A CURA DELL'INSTALLATORE
DASHED LINES SHOW THE CONNECTIONS TO BE CARRIED OUT BY THE INSTALLER
COLLEGAMENTI ESEGUITI IN FABBRICA
FACTORY CONNECTIONS
Bianco / White = Comune / Common
Rosso / Red = Bassa vel. / Low speed
Blu / Blue = Media vel. / Medium speed
Nero / Black = Max vel . / Max speed
C
L
M H
Giallo-Verde / Yellow-Green = Terra / PE
C = comune ventilatori/ fan
Ph = fase / phase
Ph1 = comune relé/
L = bassa velocità /
C
Ph
Ph1
L
M
H
M = media velocità /
H = alta velocità /
P04 = 1
P05 = 2
C07 = 0
Spostare il jumper JP1 nella posizione JP2 (alimentazione 24V) / Move jumper JP1 to position JP2 (24V power supply)
Model 15 - 43
M
1 ~
common
CP - Comfort/V
relays common
low speed
L
N
3
medium speed
high speed
0
24V ~
24
(ALSO CONSULT THE INSTRUCTION MANUAL OF THE CONTROL PANEL)
P06 = 0
P07 = 0
Solo con sonda a canale /
16
EN
VENTILATORE
MANDATA
SUPPLY FAN
Sonda a canale (NTC 10k @ 25°)
Supply duct sensor (NTC 10k @ 25°)
4
5
6 7 8 9
10
11
12
13
14
15
16
Sc
Sc
0..10V
0..10V
Only with duct sensor: P11 = 1