INSTALLATION

2.6 Electrical connections

The BAG
3
is prearranged with rubber cable feed-throughs (1) located
in the top section of the box allowing wiring to be passed through.
Below is an explanation of how to correctly connect the BAG
the boiler and on devices.
9
Before carrying out any electrical intervention, set the main
system switch to "off".
Connecting the BAG
3
to the electrical power supply
− Pass the cable (2) which comes out of the electrical con-
nection box (3) through the cable feed-through (1) and
connect it to the electrical power supply (phase-neutral-
earth) making sure not to connect it below the boiler fuse.
2
3
3
Access to the BAG
connection terminals
3
− To access the BAG
connection terminals, loosen the four
screws (4) and remove the cover (3).
3
Connecting the BAG
to the ambient thermostats/chrono-thermostats
− Carry out the connections of the ambient thermostats (TA)
and/or chrono-thermostats (CT) of each zone, as indicat-
ed in the diagram below. Before connection, eliminate
the relative jumper (TA1,TA2 or TAt3).
3
BAG
2 MIX BASIC
TA2 nero
5
TA2 dopo aver
rimosso
ponticello
NERO
in morsettiera
1
4
3
TA3 grigio
TA1 rosso
3
1
4
2
Cavo ingresso
di rete 230V
TA1 dopo aver
TA3 dopo aver
rimosso
rimosso
ponticello
ponticello
ROSSO
GRIGIO
in morsettiera
in morsettiera
3
BAG
MIX BASIC
1
1
3
on
9
The ambient thermostats (TA) and/or chrono-thermostats
(CT) of the low and high temperature systems must be con-
4
nected directly to the BAG
section of 1 mm
9
The load represented by the pump will weigh directly on the
3
corresponding ambient thermostat (TA) and/or chrono-ther-
mostat (CT), therefore the TA and/or CT contact must be adapt-
ed to the application and be compatible with the electrical
rate of the pump not less than 6A (230Vac-50Hz).
Connecting the BAG
− Connect the CONNECT LE to the boiler (GEN) as indicated in
the diagram below.
9
Connect the mammut (B-B) of the BAG
of the boiler using a cable with a minimum section of 2x0.5
mm
(please refer to the wiring diagram in the instruction
2
booklet for the installer of the specific boiler).
9
When using a phase-phase power supply, use a tester to
determine which of the two wires has the greater potential
compared to the earth and connect it to the L terminal. Con-
nect the remaining wire to the N terminal.
9
For floating power supplies, i.e. those which have no earth
connection, an insulation transformer must be used with a
secondary unit connected to the earth.
9
It is mandatory:
− to use a multi-pole trip-switch to disconnect the line in
compliance with CEI-EN standards (contact opening at
least 3 mm)
− to use cables with a 1.5 mm
(phase) - N (neutral) connection
− that the amperage on the switch is adequate for the boil-
26
TA1 rosso
TA3 grigio
3
1
5
4
2
TBT 1
TA1 dopo aver
TA3 dopo aver
rimosso
rimosso
ponticello
ponticello
ROSSO
GRIGIO
in morsettiera
in morsettiera
3
using a cable with a minimum
.
2
3
to the boiler
INGRESSO RICHIESTA
CALORE
CALDAIA o GENERATORE
nero
nero
g/v
g/v
blu
blu
blu
marrone
marrone
marrone
Fusibile 3.15A F
3
to the mammut (TA)
2
section and respect the L
Cavo ingresso
di rete 230V