Commissioning; First Start-Up; Setting The Circulation Units - Riello BAG3 MIX BASIC Instructions For The Installaer And For Technical Assistance

Table of Contents

Advertisement

Available languages

Available languages

er's electrical power rating. Please refer to the technical
data to check
− the electrical power rating for the model installed
− to connect the appliance to an efficient earthing system
− to ensure that access to the power socket is protected af-
ter installation.
0
The use of gas or water pipes to earth this appliance is strict-
ly prohibited.
9
The manufacturer declines any liability for damage caused
due to the lack of a proper earthing system or failure to
comply with the wiring diagrams.Commissioning.

3 COMMISSIONING

3.1 First start-up

3
Before starting up the BAG
trical connections have been carried out correctly.
During the testing phase it is possible to check the temperatures
of the low temperature zones using the thermometers (T1-T2).
T1
3.2

Setting the circulation units

The BAG
3
is equipped with digitally controlled high efficiency
electronic circulation units. Below is a description of the main
characteristics and the procedures to be carried out in order to
set the required operation.
User interface
The user interface consists of a button (A), a two-colour LED red/
purple (B) and four yellow LED (C).
A
The user interface allows the functions which are in operation
to be displayed (operating status, alarm status) and allows the
circulation unit operating mode to be set.
The performance data, indicated by the LED (B) and (C) is al-
ways displayed during normal operation of the circulation
units while the parameters are set by pressing the button (A).
Indication of the operating status
When the circulation unit is operating, the LED (B) is green The
four yellow LEDs (C) indicate the consumption of electrical energy
(P1) as shown in the table below.
, check that the plumbing and elec-
T2
C2
B
C
C1
LED status
Green LED on +
1 yellow LED on
Green LED on +
2 yellow LED on
Green LED on +
3 yellow LED on
Green LED on +
4 yellow LED on
(*) For the power (P1) absorbed by the individual circulation
unit, please refer to the information provided in the table
"Technical data" page 19 .
ndication of the alarm status
If the circulation unit has detected one or more than one alarm,
the two-colour LED (B) is red. The four yellow LEDs (C) indicate the
type of alarm as shown in the table below.
ALARM
LED status
description
Red LED
Motor shaft is
on +
blocked
LED 5 yellow on
Red LED
Low input
on +
voltage
LED 4 yellow on
Red LED
Fault in the
on +
electrical power
LED 3 yellow
supply or faulty
on
circulation unit
9
If more than one alarm activates, the circulation unit will
only display the alarm with the highest priority.
Active settings display
With the circulation unit powered, briefly press the button (A)
to see the active configuration of the circulation unit. The LEDs
indicate the active settings.
No changes can be made to the configuration of the circulation
unit in this phase. Two seconds after having pressed the button
(A), the user interface once again shows the normal display of
the operating status.
Button lock function
The button lock function is used to prevent any setting modifi-
cation being made accidentally or improper use of the circula-
tion unit.
When the button lock function is active, it is not possible to press
and hold the button (A). This prevents from entering the settings
section of the circulation unit operating modes.
Pressing the button (A) for more than 10 seconds enables/dis-
ables the button lock function. During this passage, all LEDs (C)
flash for 1 second.
> 10 s
27
COMMISSIONING
Consumption
CIRCULATION UNIT
in % of
status
P1 MAX (*)
Operation at minimum
0-25
Operation at
25-50
minimum-average
Operation at
50-75
average-maximum
Operation at maximum
100
CIRCULATION
Possible
UNIT status
SOLUTION
Attempt
Wait or re-
start-up
lease motor
every 1.5 sec-
shaft
onds
Warning
only. The cir-
Check the in-
culation unit
put voltage
continues to
operate
Check the
electrical
The circula-
power supply
tion unit is
or replace
not moving
the circula-
tion unit