Mitsubishi Electric FR-V500 Series Instruction Manual page 68

Vector inverter
Hide thumbs Also See for FR-V500 Series:
Table of Contents

Advertisement

Name
168
Maker setting parameters. Do not set.
169
Actual operation hour
171
You can clear the actual operation hour meter.
meter clear
You can select the following input signals.
0: RL (multi-speed low-speed run command) → Pr. 180 factory setting
DI1 terminal function
180
1: RM (multi-speed middle-speed run command) → Pr. 181 factory setting
selection
2: RH (multi-speed high-speed run command) → Pr. 182 factory setting
3: RT (second function selection) → Pr. 183 factory setting
5: JOG (jog operation selection)
8: REX (multi-speed 15 speeds selection)
DI2 terminal function
181
9: X9 (third function selection)
selection
10: X10 (FR-HC,FR-CV connection (inverter run enable signal))
11: X11 (FR-HC connection (instantaneous power failure detection)
12: X12 (PU operation external interlock)
14: X14 (PID control valid)
DI3 terminal function
15: BRI (brake release completion signal)
182
selection
16: X16 (PU operation-external operation switchover)
20: X20 (S-pattern acceleration/deceleration C switching terminal)
22: X22 (orientation command)
23: LX (pre-excitation/servo on)
DI4 terminal function
24:MRS(output stop)
183
25: STOP (start self-holding selection)
selection
26: MC (control mode switching)
27: TL (torque limit selection)
28: X28 (start time tuning)
42: X42 (torque bias selection 1)
STR terminal function
187
43: X43 (torque bias selection 2)
selection
44: X44 (P control selection (P/PI control switching))
9999: No function (STR when set in Pr. 187)
You can select the following output signals.
0 (positive logic) → Pr. 190 factory setting, 100 (negative logic): RUN (inverter running)
1 (positive logic) → Pr. 191 factory setting, 101 (negative logic): SU (up to speed)
2 (positive logic) → Pr. 192 factory setting, 102 (negative logic): IPF (instantaneous
DO1 terminal function
power failure or undervoltage)
190
selection
3 (positive logic), 103 (negative logic) : OL (overload warning)
4 (positive logic), 104 (negative logic) : FU (output speed detection)
5 (positive logic), 105 (negative logic) : FU2 (second output speed detection)
6 (positive logic), 106 (negative logic) : FU3 (third output speed detection)
7 (positive logic), 107 (negative logic) : RBP (regenerative brake prealarm)
8 (positive logic), 108 (negative logic) : THP (electronic thermal relay function prealarm)
10 (positive logic), 110 (negative logic) : PU (PU operation mode)
11 (positive logic), 111 (negative logic) : RY (inverter operation ready)
12 (positive logic), 112 (negative logic) : Y12 (output current detection)
DO2 terminal function
13 (positive logic), 113 (negative logic) : Y13 (zero current detection)
191
14 (positive logic), 114 (negative logic) : FDN (PID lower limit)
selection
15 (positive logic), 115 (negative logic) : FUP (PID upper limit)
16 (positive logic), 116 (negative logic) : RL (PID forward/reverse rotation output)
20 (positive logic), 120 (negative logic) : BOF (brake opening request)
25 (positive logic), 125 (negative logic) : FAN (fan failure output)
26 (positive logic), 126 (negative logic) : FIN (heatsink overheat prealarm)
27 (positive logic), 127 (negative logic) : ORA (orientation completion)
30 (positive logic), 130 (negative logic) : Y30 (forward rotation output)
31 (positive logic), 131 (negative logic) : Y31 (reverse rotation output)
32 (positive logic), 132 (negative logic) : Y32 (regenerative status output)
DO3 terminal function
33 (positive logic), 133 (negative logic) : RY2 (operation ready 2)
192
selection
34 (positive logic), 134 (negative logic) : LS (low speed output)
35 (positive logic), 135 (negative logic) : TU (torque detection)
36 (positive logic), 136 (negative logic) : Y36 (in-position)
37 (positive logic), 137 (negative logic) : MT (maintenance timer output)
39 (positive logic), 139 (negative logic) : Y39 (start time tuning completion)
40 (positive logic), 140 (negative logic) : Y40:(trace status)
41 (positive logic), 141 (negative logic) : FB (speed detection)
42 (positive logic), 142 (negative logic) : FB2 (second speed detection)
43 (positive logic), 143 (negative logic) : FB3 (third speed detection)
A,B,C terminal
44 (positive logic), 144 (negative logic) : RUN2 (second inveter operating)
195
96 (positive logic), 196 (negative logic) : REM (remote output)
function selection
97 (positive logic), 197 (negative logic) : ER (minor fault output 2)
98 (positive logic), 198 (negative logic) : LF (minor fault output)
99 (positive logic) → Pr. 195 factory setting, 199 (negative logic): ABC (alarm output)
9999: No function
Function list (Extended function parameters)
Outline
65
At-a-glance Guide to
Functions
: Usable function
× : Unusable function
Cus-
* : Functions that can be used
Factory
tomer
for parameter-set position
Setting
Set-
control
ting
Vector Control
Speed
Torque
control
control
0
0
1
2
3
9999
0
1
2
99
Position
control
5