Parameter
Name
22
Torque limit level
Set resolution
811
switchover
Torque limit level
812
(regeneration)
Torque limit level
813
(3rd quadrant)
Torque limit level
814
(4th quadrant)
815
Torque limit level 2
Acceleration torque
816
limit level
Deceleration torque
817
limit level
(1) Torque limit level
1)
When Pr. 810 = 0
In the factory setting, limit is made on all
quadrants on the Pr. 22 torque limit level.
When you want to set the level on a quadrant
basis, change the corresponding parameter
value.
Torque limit
Reverse
regeneration
Reverse
quad 1
quad 4
rotation
(Pr. 814)
(Pr. 22)
quad 3
quad 2
(Pr. 813)
(Pr. 812)
Reverse
driving
1500
1500
-
r/min
r/min
Factory
Setting
Set the torque limit level in % for speed control or position control so that the
output torque does not exceed the predetermined value. (0 to 400%)
When Pr. 810 = 0,
150
The setting increments of Pr. 22 "torque limit level" and Pr. 812 to Pr. 817
(torque limit level) and the speed from the communication can be changed.
0: Torque limit 0.1% increments;
Speed from the communication 1r/min increments
1: Torque limit 0.1% increments;
0
Speed from the communication 0.1r/min increments
10: Torque limit 0.01% increments;
Speed from the communication 1r/min increments
11: Torque limit 0.01% increments;
Speed from the communication 0.1r/min increments
Set the torque limit level in % for regeneration. (0 to 400%)
9999
Valid for regeneration when Pr. 810 = 0.
9999: Restricted to the Pr. 22 value.
Set the torque limit level in % for 3rd quadrant. (0 to 400%)
9999
Valid for reverse rotation driving when Pr. 810 = 0.
9999: Restricted to the Pr. 22 value.
Set the torque limit level in % for 4th quadrant. (0 to 400%)
9999
Valid for reverse rotation regeneration when Pr. 810 = 0.
9999: Restricted to the Pr. 22 value.
When the TL signal is on, the Pr. 815 value is a torque limit value regardless
of Pr. 810.
9999
Set the torque limit level in % for all operations. (0 to 400%)
Valid when the TL terminal (torque limit selection) input is provided.
9999: According to the Pr. 22 value.
Set the torque limit value for acceleration.
9999
9999: Same torque limit as at constant speed
Set the torque limit value for deceleration.
9999
9999: Same torque limit as at constant speed
2)
When Pr. 810 = 1
With the upper limit of torque limit as set in Pr. 22, the analog
input from the terminal 3 input is used as the torque limit
value within the Pr. 22 setting range. When the torque limit
function is selected in the regenerative mode with the
terminal 1 selected, the input from the terminal 1 is used as
the torque limit on the regenerative side. (Pr. 868 = 2)
Forward
Reverse
driving
regeneration
Terminal 1 input or Pr. 22
Forward
whichever is smaller
rotation
Reverse rotation
Speed
Speed
Terminal 3 input
or Pr. 22
Forward
Reverse
regeneration
driving
35
Speed control operation
Description
1st quadrant Pr. 22
2nd quadrant Pr. 812
3rd quadrant Pr. 813
4th quadrant Pr. 814
Torque limit
quad 4
quad 1
1500
quad 3
quad 2
r/min
-
Forward
driving
Terminal 3 input or Pr. 22
whichever is smaller
Forward rotation
1500r/min
Terminal 1 input or Pr. 22
whichever is smaller
Forward
regeneration
4