2) Wiring
Do not fit capacitive equipment such as power factor correction capacitor, surge suppressor or radio noise filter (option FR-BIF) to
the inverter output side.
The connection orientation of the output cables (terminals U, V, W) to the motor will affect the direction of rotation of the motor.
3) Trial run
Check all parameters, and ensure that the machine will not be damaged by a sudden start-up.
4) Operation
When you have chosen the retry function, stay away from the equipment as it will restart suddenly after an alarm stop.
Since the [STOP] key is valid only when functions are set (refer to page 62) provide a circuit and switch separately to make an
emergency stop (power off, mechanical brake operation for emergency stop, etc).
Make sure that the start signal is off before resetting the inverter alarm. A failure to do so may restart the motor suddenly.
The load used should be a three-phase induction motor only. Connection of any other electrical equipment to the inverter output may
damage the equipment.
Do not modify the equipment.
Do not perform parts removal which is not instructed in this manual. Doing so may lead to fault or damage of the inverter.
The electronic thermal relay function does not guarantee protection of the motor from overheating.
Do not use a magnetic contactor on the inverter input for frequent starting/stopping of the inverter.
Use a noise filter to reduce the effect of electromagnetic interference. Otherwise nearby electronic equipment may be affected.
Take measures to suppress harmonics. Otherwise power supply harmonics from the inverter may heat/damage the power capacitor
and generator.
When a 400V class motor is inverter-driven, please use an insulation-enhanced motor or measures taken to suppress surge
voltages. Surge voltages attributable to the wiring constants may occur at the motor terminals, deteriorating the insulation of the
motor.
When parameter clear or all clear is performed, each parameter returns to the factory setting. Each parameter returns to the factory
setting.
The inverter can be easily set for high-speed operation. Before changing its setting, fully examine the performances of the motor and machine.
In addition to the inverter's holding function, install a holding device to ensure safety.
Before running an inverter which had been stored for a long period, always perform inspection and test operation. In addition to the
inverter's holding function, install a holding device to ensure safety.
5) Emergency stop
Provide a safety backup such as an emergency brake which will prevent the machine and equipment from hazardous conditions if
the inverter fails.
When the breaker on the inverter input side trips, check for the wiring fault (short circuit), damage to internal parts of the inverter, etc.
Identify the cause of the trip, then remove the cause and power on the breaker.
When the protective function is activated, take the appropriate corrective action, then reset the inverter, and resume operation.
6) Maintenance, inspection and parts replacement
Do not carry out a megger (insulation resistance) test on the control circuit of the inverter.
7) Disposing of the inverter
Treat as industrial waste.
8) General instructions
Many of the diagrams and drawings in this Instruction Manual (basic) show the inverter without a cover, or partially open. Never operate
the inverter in this manner. Always replace the cover and follow this Instruction Manual (basic) when operating the inverter.
<Abbreviations>
DU: Control panel (FR-DU04
PU: Control panel (FR-DU04
Inverter: Mitsubishi vector inverter FR-V500 series
FR-V500: Mitsubishi vector inverter FR-V500 series
Pr.: Parameter number
PU operation: Operation using the PU (FR-DU04
External operation: Operation using the control circuit signals
Combined operation: Operation using both the PU (FR-DU04
<Trademarks>
CC-Link is a registered trademark of CC-Link Partner Association.
Other company and product names herein are the trademarks or registerd trademarks of their respective owners.
)
-1
) and parameter unit (FR-PU04V)
-1
/FR-PU04V)
-1
CAUTION
CAUTION
WARNING
CAUTION
CAUTION
CAUTION
CAUTION
/FR-PU04V) and external operation
-1
A-2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents