Alarm Overview - Swegon Free V90 Installation Manual

Air handling unit
Table of Contents

Advertisement

Alarmlist
No action may be carried out before the unit stopped, and the power is off!
Any error that is indicated to be checked and fixed!
LEDs for alarm and Operation flashes in different ways depending on which alarm has been triggered.
Numeric display indicates the alarm code.
The alarm is reset by pressing and holding the Comfort panel fan control + and - buttons for about 5 seconds.
Filter alarm is reset by pressing and holding the Comfort panel temperature control + and - buttons for about 5 seconds.
Alarm
Content
nr.
1
Emergency stop triggred
2
Internal fire alarm
3
Anti freeze protection (Out < +7°C)
3
Anti freeze protection (Out > +7°C)
4
Rotation guard triggred (Out <+5°C)
4
Rotation guard triggred (Out >+5°C)
5
Anti freeze protection guard defective
6
Temperature sensor defective
7
Eletrical heater triggred
8
Exhaust temperature under setpoint
8
Exhaust temperature under setpoint
9
Supply temperature under setpoint
9
Supply air temperature deviates from
the setpoint
10
Supply airflow below setpoint
11
Exhaust airflow below setpoint
12
Supply/exhaust filter clogged
12
Supply/exhaust filter clogged
12
Supply/exhaust filter clogged
13
External stop
26
Indication on
The service technician:
led
See the service manual how to fix the alarms.
Alarm: Shines
All functions are stopped without delay. Check the electric bat-
Drift: Off
tery when no cooling is done. Check reason to stop!
Alarm: Shines
Check the unit's internal components. The alarm stops the unit
Drift: Off
in case of fire in the property, not to spread the smoke / fire.
Alarm: Shines
Check water temp to the coil and/or heat recovery
Drift: Off
Alarm: Flashes
Check water temp to the coil and/or heat recovery
Drift: Shines
Alarm: Shines
Check that the rotor spins easily, drive belt, rotor guard
Drift: Off
indication and cabling.
Alarm: Flashes
Check that the rotor spins easily, drive belt, rotor guard
Drift: Shines
indication and cabling
Alarm: Shines
Check connection or replace the sensor.
Drift: Off
Alarm: Shines
Check connection or replace the sensor.
Drift: Off
Alarm: Shines
Thermal protection is activated, investigate the reason!
Drift: Off
Alarm: Shines
Check exhaust temperature, minimum +15°C and/or airflow.
Drift: Off
Check DIP-switch 4 so correct Fan (1/2) are chosen for supply
Alarm: Flashes
Check exhaust temperature, minimum +15°C and/or airflow.
Drift: Shines
Check DIP-switch 4 so correct Fan (1/2) are chosen for supply
Alarm: Shines
Check heater and recovery funktion
Drift: Off
Alarm: Flashes
Check the recovery function and and coils.
Drift: Shines
Alarm: Shines
Check the supply fan operation.
Drift: Off
Check the supply air duct system.
Alarm: Shines
Check the exhaust fan function.
Drift: Off
Check the exhaust air duct system.
Alarm: Shines
Unit stops when filter are clogged
Drift: Off
Alarm: Flashes
Filter Alarms - the unit stops in a month if no filter is changed.
Drift: Shines
Alarm: Off
Indicates that the filter should be changed.
Drift: Shines
Alarm: Shines
External stop function activated
Drift: Off