Airflow settings and adjustment
Start sequence of the unit
The LED flashes for operation when the unit
is in the startup phase, wait about 3 minutes.
When the LED is steady, the unit is in opera-
tion mode.
The unit then starts aligned with the parame-
ters.
Operation with electric heating coil
The controller keeps a constant temperature
by means of the supply air sensor placed in
the duct after the heater.
Control is done in sequence, heat exchanger
recovers heat from exhaust air to preheat
incoming air.
If supply air dont reach the correct tempera-
ture, the electric heater gets its start signal to
help to reach the optimal supply air temp.
At normal stop, the fans run for 3 minutes to
cool the electric heater before the unit stops.
IMPORTANT
If the unit is equipped with electric heater, nor-
mal airflow should always be greater than the
minimum airflow according to the graph on page
22.
Manufacturer reserves the right to alter specifications
Operation with water-heating coil
The controller keeps a constant temperature
by means of the supply air sensor placed in
the duct after the battery.
Control is done in sequence, heat exchanger
recovers heat from exhaust air to preheat
incoming air.
If supply air do not reach the correct tempe-
rature, the circulation pump starts and water
heater actuators starts to opens the flow of
water over the heater.
To protect the coil from freezing is a frost
guard sensor adapted to the return line to the
water heater. If the temperature will be below
7°C, the unit stops.
This sensor also helps to constantly keep the
battery temperature to 20°C when ventilation
is turned off.
Anti-jamming of circulation pump with 3 min
/ day.
Operation with water cooler
The cooling function is activated manually
using the Comfort panel, choose Cool.
The cooling function will start the circulation
pump for the cooling circuit and the cooling
coil actuator opens.
The actuator controls the flow of cooling wa-
ter to the battery using the supply air sensor
so that the desired temperature is reached.
If the temperature of the air inside the pro-
perty is less than the temperature of the
outside air by 2°C, the heat exchanger runs
cooling recover from the lower exhaust tem-
perature.
Anti-jamming of circulation pump with 3 min
/ day.
23