Download Print this page

Swegon TBLE Series Installation

Electric air heater gold sizes 11-32

Advertisement

Quick Links

INSTALLATION –TBLE ELECTRIC AIR HEATER
GOLD Sizes 11-32
CONNECT TO THE DUCTING
1. The heater should be connected to the ducting as fol-
lows:
a) TBLE 000-031 and 000-040
The electric heater is designed for connection directly to
spiral ducts. Secure the heater to the ducting by means of
pop rivets.
b) TBLE 080-040 and 120-060
The electric air heater can be fitted in the ducting or
directly to the air handling unit. Secure the electric heater
with a sealing strip and slip clamps with PG connection.
2. The airflow direction through the electric heater must
be according to the arrow on the side of the heater, at the
base of the junction box.
3. The electric heater can be installed in a horizontal or
a vertical duct, with the junction box either upward or
turned within 90° toward either side. Installation with the
junction box facing downward is not permissible.
4. The electric air heater should be located at a distance
to or from a duct bend, damper, filter or similar compo-
nent. This distance should be at least equivalent to
a) double the duct diameter (TBLE 000-031 and
000-040).
b) its cross-section measured diagonally, i.e. from corner
to corner in the in-duct section of the
080-040 och 120-060).
Otherwise, there is a risk that the air stream through the
heater won't be uniform and this may cause the overhea-
ting protection to trip.
5. The electric air heater must be insulated according to
local ventilation ducting standards. The heater must be
insulated with incombustible insulation material. The
insulation must not conceal the cover, since the rating
plate must be visible and it must be possible to remove the
cover.
6. The in-duct section with built-in heating element must
be accessible for replacement and inspection.
7. The distance from the metal casing of the electric air
heater to wood or any other combustible material must
not be less than 30 mm.
Specifications are subject to alteration without notice.
OPERATION
The TBLE electric air heater has a built-in thyristor that is
controlled across a 0–10 Volt signal from the GOLD unit.
The electric heater has two overheating protections wired
in series. One resets itself automatically; the other must be
manually reset. These protections are designed to prevent
excessively high temperature if the airflow should become
too low and are designed to prevent overheating in the
event of some system malfunction.
The control signal and overheating protection can be
wired to the GOLD unit across a cable with connector.
If overheating protection trips, an alarm indication will be
visible in the hand-held terminal of the GOLD unit. Find
the cause of the fault and take remedial action. Press the
reset button on the heater to reset the overheating pro-
tection and then press the reset button on the hand-held
terminal.
TBLE
heater. (TBLE
GB.TBLE-B.050101
www.swegon.se
1

Advertisement

loading

Summary of Contents for Swegon TBLE Series

  • Page 1 7. The distance from the metal casing of the electric air heater to wood or any other combustible material must not be less than 30 mm. www.swegon.se Specifications are subject to alteration without notice.
  • Page 2 TBLE 000-031, matches GOLD sizes 11, 12 TBLE 000-040, matches GOLD size 15 ��� ����� �� �� 080-040 1019 ��� 120-060 1419 1200 000-031 000-040-060 000-040-120-1 ��� TBLE-000-040-120-2 �� �� �� �� ��� �� ��� www.swegon.se Specifications are subject to alteration without notice.
  • Page 3 = Control signal M (0 V) Blue = Overheating White-orange = Overheating Green = Type of heater (resistance) Control cable White-green = Type of heater (prewired) Applicable to the 27 – 47.5 kW electric air heaters www.swegon.se Specifications are subject to alteration without notice.
  • Page 4 = Control signal M (0 V) Blue = Overheating White-orange = Overheating Control cable Green = Type of heater (resistance) (prewired) White-green = Type of heater Applicable to the 27 – 47.5 kW electric air heaters www.swegon.se Specifications are subject to alteration without notice.

This manual is also suitable for:

Tble 000-031Tble 000-04Tble 080-040Tble 120-060Tble 000-040-060Tble 000-040-120-1