Download Print this page

Swegon TBLE Series Installation page 4

Electric air heater gold sizes 11-32

Advertisement

3 X 230V
Type
TBLE-000-031-030-2
TBLE-000-031-045-2
TBLE-000-031-075-2
TBLE-000-040-060-2
TBLE-000-040-120-2
TBLE-080-040-080-2
TBLE-080-040-120-2
TBLE-080-040-200-2
TBLE-120-060-120-2
TBLE-120-060-200-2
TBLE-120-060-270-2
TBLE-120-060-360-2
TBLE-120-060-475-2
Brown
= 24 V~(G)
White-brown
= 24 V~(G0)
Orange
= Control signal Y (0-10 V)
White-blue
= Control signal M (0 V)
Blue
= Overheating
White-orange
= Overheating
Green
= Type of heater (resistance)
White-green
= Type of heater
4
www.swegon.se
Output
Supply
3 kW
3 X 230V + earth
4.5 kW
3 X 230V + earth
7.5 kW
3 X 230V + earth
6,0 kW
3 X 230V + earth
12,0 kW
3 X 230V + earth
8 kW
3 X 230V + earth
12 kW
3 X 230V + earth
20 kW
3 X 230V + earth
12 kW
3 X 230V + earth
20 kW
3 X 230V + earth
27 kW
3 X 230V + earth
36 kW
3 X 230V + earth
47,5 kW
3 X 230V + earth
Current
Fuse
7.5 A
10 A
11.3 A
16 A
18.8 A
25 A
15 A
20 A
30,1 A
32 A
20.1 A
25 A
30,1 A
32 A
50.2 A
63 A
Applicable to electric air heaters up to 20 kW
30,1 A
32 A
50.2 A
63 A
67.8 A
80 A
90,5 A
100 A
119,2 A
125 A
Applicable to the 27 – 47.5 kW electric air heaters
Specifications are subject to alteration without notice.
GB.TBLE-B.050101
Control unit in
electric air heater
��
��
�� ��
� �
15
Control cable
(prewired)
Control unit in
electric air heater
��
��
�� ��
3
� �
Control cable
(prewired)
16
4
10 KΩ

Advertisement

loading

This manual is also suitable for:

Tble 000-031Tble 000-04Tble 080-040Tble 120-060Tble 000-040-060Tble 000-040-120-1