Function Guide for the GOLD,
Preheating
1. General
When it is cold outside and the humidity is high, preheat-
ing the incoming outdoor air will prevent condensation
from forming on outdoor air filter surfaces in the air han-
dling unit.
Preheating the air also reduces the risk of frosting in the
heat exchanger.
Preheating the outdoor air may also be required during
periods of extremely low temperatures outside. If the air is
preheated to -20°C, for instance, this prevents the pres-
sure sensor and the frequency inverter from having to
operate under excessively low ambient temperature condi-
tions.
The preheating function can control the air heater as fol-
lows:
– Electric air heater, pause/pulse control signal.
– Electric air heater, 0–10 V.
– Air heater for hot water, 0-10 V control signal, with anti-
frost monitor/heat retaining function.
– Air heater for hot water, 0-10 V control signal, without
anti-frost monitor/heat retaining function.
Type TBLF air heaters for preheating are designed for
installation in an outdoor air duct, however they can also
be installed in an exhaust air or extract air duct.
Preheating is interlocked to follow the supply air flow. This
means that the function cannot be used in the exhaust air
or extract air duct while the supply air fan is switched off
and the extract air fan alone is operating.
The preheating function has a relay function for control-
ling a circulation pump, if required.
Specifications are subject to change without notice.
2. Material Specification
Air handling unit
Option 1
Air heater, water, for preheating
The TBLZ-1-53-1 Control of air heater for preheating is
included.
or
Air heater, water,
for preheating (not size 50-120)
The TBLZ-1-53-1 Control of air heater for preheating is
included.
Option 2
Electric air heater, type Swegon standard,
for preheating (not size 50-120)
Control of air heater for preheating.
Consists of: IQnomic Plus, TBIQ-2-1
Temperature sensor (set) for duct mounting,
TBLZ-1-30.
Communication cable, BC1-1 (L = 250 mm).
Without anti-frost monitor sensor
Jack, modular/terminal block
Option 3
Air heater of other type than TBLF/TCLF or TBLE.
Control of air heater for preheating.
Consists of: IQnomic Plus, TBIQ-2-1
Temperature sensor (set) for duct mounting,
TBLZ-1-30.
Communication cable, BC1-1 (L = 250 mm).
Code: a = 0 without anti-frost monitor sensor
a = 1 with anti-frost monitor sensor
GB.PREHEAT.130225
All types of GOLD
TBLF-1-aaa-aaa
TCLF-1-aa
TBLE
TBLZ-1-53-0
TBLZ-1-55
TBLZ-1-53-a
www.swegon.com
1

Advertisement

loading

Summary of Contents for Swegon Gold TBLE Series

  • Page 1 Option 2 The preheating function can control the air heater as fol- lows: Electric air heater, type Swegon standard, – Electric air heater, pause/pulse control signal. for preheating (not size 50-120) TBLE – Electric air heater, 0–10 V.
  • Page 2 TBLF and TCLF, the air heater can be fitted directly to the air hand- ling unit and the temperature sensor can then be mounted inside the air handling unit after the filter. www.swegon.com Specifications are subject to change without notice.
  • Page 3: Electrical Connections

    Supply voltage to 1-phase pump, max 1.5 A, can be obtained by wiring to the following terminals inside the air handling unit: GOLD: Terminal 101 (L), terminal 102 (N). COMPACT Unit & Top: Terminal 201 (L), terminal 202 (N). PE N L www.swegon.com Specifications are subject to change without notice.
  • Page 4 GB.PREHEAT.130225 Electric air heater Swegon Standard with Jack for wall mounting, control cable 8-pole, TBLZ-1-55 Temp. sensor,** for preheated air Jack for wall moun- Electric air ting, 019611 heater Swe- gon Standard with control cable, 8-pole 24 V AC* (G0) 0-10 V –...
  • Page 5: Electric Air Heater

    Function selector switch in Position 9 Communication cable to the control unit of the air handling unit, where it should be connec- ted to one of the connections 10 11 for Internal EIA-485. www.swegon.com Specifications are subject to change without notice.
  • Page 6: Installation

    DEACTIVATE EL AIR HEATER P/P EL AIR HEATER 0-10 V W. COIL WITH FP W. COIL WITHOUT FP Under “SETTINGS”, select the desired setpoint in *PREHEAT* FUNCTION, OFF/ON SETTINGS *PREHEAT* TEMPERATURE 5.0°C. www.swegon.com Specifications are subject to change without notice.
  • Page 7: Performance Checks

    GOLD unit’s control unit. 10 11 Temperature sensor: Current temperatures can be read under INSTALLATION – READINGS – IQNOMIC PLUS – PREHEAT. If the tempera- ture readings are reasonable, wiring has been carried out correctly. www.swegon.com Specifications are subject to change without notice.
  • Page 8 GB.PREHEAT.130225 www.swegon.com Specifications are subject to change without notice.