Electric air heater gold sizes 11-32

Advertisement

Electrical Connection
1. The electrical installation must be carried out by a quali-
fied electrician according to local regulations.
The electric air heater has been granted approval by
SEMKO, NEMKO, DEMKO and the Finnish Electrical Equip-
ment Inspectorate.
2. Control
The electric heater is equipped with a 5 m long control cable
that has a quick connector for connection to the GOLD unit.
An extension cable is available as an accessory.
3. Power supply
Connect the heater directly to the power supply (across
a safety switch, if required) in accordance with the tables
and illustrations below.
2 X 400V
Type
Output
TBLE-000-031-030-1
3 kW
TBLE-000-031-045-1
4.5 kW
3 X 400V
Type
Output
TBLE-000-031-075-1
7.5 kW
TBLE-000-040-060-1
6,0 kW
TBLE-000-040-120-1
12,0 kW
TBLE-080-040-080-1
8 kW
TBLE-080-040-120-1
12 kW
TBLE-080-040-200-1
20 kW
TBLE-120-060-120-1
12 kW
TBLE-120-060-200-1
20 kW
TBLE-120-060-270-1
27 kW
TBLE-120-060-360-1
36 kW
TBLE-120-060-475-1
47,5 kW
Brown
= 24 V~(G)
White-brown
= 24 V~(G0)
Orange
= Control signal Y (0-10 V)
White-blue
= Control signal M (0 V)
Blue
= Overheating
White-orange
= Overheating
Green
= Type of heater (resistance)
White-green
= Type of heater
Specifications are subject to alteration without notice.
Supply
Current
2 X 400V + earth
7.5 A
2 X 400V + earth
11.3 A
Supply
Current
3 X 400V + N + earth
10,8 A
3 X 400V + N + earth 8,7 A
3 X 400V + N + earth
17,3 A
3 X 400V + N + earth
11.6 A
3 X 400V + N + earth
17.3 A
3 X 400V + N + earth
28.9 A
3 X 400V + N + earth
17,3 A
3 X 400V + N + earth
28.9 A
3 X 400V + N + earth
39.0 A
3 X 400V + N + earth 52,0 A
3 X 400V + N + earth 68,6 A
�� ��
Fuse
10 A
16 A
Control cable
(prewired)
Fuse
�� ��
16 A
10 A
20 A
16 A
20 A
32 A
Control cable
20 A
(prewired)
32 A
Applicable to electric air heaters up to 20 kW
50 A
63 A
80 A
�� ��
Control cable
(prewired)
Applicable to the 27 – 47.5 kW electric air heaters
GB.TBLE-B.050101
Control unit in
electric air heater
��
��
� �
15
16
Control unit in
electric air heater
��
��
� �
15
16
Control unit in
electric air heater
��
��
3
4
� �
10 KΩ