NOTE: The cycles are symmetrical for Vessel A and Vessel B:
Steps 9 -16 are a repeat of Steps 1-8, but with 'A' and 'B' side tags switched.
After Step 16, the controller will continue back to Step 1. Note that the Step 7 & 15: Energy Saving function is only
applicable if it has been enabled in SETTINGS (under the Energy Management option). To enable this, refer to the
SETTINGS section of the manual.
If a power interruption occurs while the dryer is in operation, the inlet and regeneration valves will not move. The
depressurization valve will return normally open and the depressurization valves will return normally closed. Upon
power startup, the dryer will remember its sequence step and continue where it left off.
5.4.4
Controller Settings
SETTINGS
Within the SETTINGS function of the controller, the system can be configured based on several characteristics that will
affect the operation of dryer:
Global Setting: Date/Time; Language; Units of Measure
Parameters: Regeneration Control; Communication; Energy Report
DRYPOINT XFi 1000 manual_revA EN
28