Loading the Configuration File

The supplied archive "109739240_RTU3041C_ PROJ_V30.zip" contains the
finished configuration file ("*.cfg"), which you can load into your RTU3041C and
adapt to your application in just a few steps.
To load the supplied configuration into your RTU3041C, proceed as follows:
1. Connect the RTU3041C to your PG/PC via a network cable.
Note
Ensure that only one RTU is connected to your network at a time during
commissioning, as each RTU is assigned the same IP address at the factory.
2. If necessary, change the IP address of your PG/PC (according to
that it and the RTU3041C are in the same subnet.
The factory default IP address "192.168.0.3" is set in the RTU3041C.
3. Wake up the RTU3041C by briefly pressing the WKUP/RESET button on the
RTU.
4. In a browser, open the web server of the RTU3041C at the address
"192.168.0.3".
5. Log in with the username "admin" and the password "admin".
6. Assign a new password.
7. Navigate to the "Maintenance" menu.
8. Under "Load configuration", click "Search".
9. Select the downloaded configuration file.
10. Confirm with "Ok".
Monitoring of Remote Measurement Points
Entry ID: 109739240,
V3.0,
06/2021