Download Print this page

External Connection - Toshiba GF642 Manual

Electromagnetic flowmeter

Advertisement

EJL-146C

External Connection

Instrument panel : Ordered separately
Grounding with 100Ω or less
ground resistance
Power switch
(External double-pole power switch)
Power supply
Current output (4~20mAdc)
or PROFIBUS
Digital input
(20~30Vdc)
or Modbus
Digital output 2
Signal common for DI and DO
Digital output 1
Grounding with 100Ω or less
ground resistance
Figure 4. Separate type LF642/LF622 flowmeters wiring Diagram
6
Power cable
I/O cable
Symbol
Description
L1 (+)
Power supply
L2 (-)
GND
Ground (for arrester)
FG
Frame ground
DI
Digital Input (20~30Vdc)
DO1
Digital Output 1
DO2
Digital Output 2
COM
Signal Common for DI, DO1, DO2
Current Output (4~20mAdc)
or PROFIBUS
X
Y
Excitation Output
E
A
B
Signal Input
G
Symbol
Description
T+
Modbus(+)
T-
Modbus(-)
TG
Modbus(GND)
Ⅳ wire 5.5mm
Grounding with 100Ω or less
ground resistance
Thick walled steel conduit
Signal cable
(2-wire shielded hard-rubber sheathed cable)
Excitation cable
(3-wire shielded hard-rubber cable)
Connected detector
Cable
Power cable
I/O cable
Shielded cable for
PROFIBUS-PA
Excitation cable
(for LF622, LF622F only)
Signal cable
(for LF622, LF622F only)
Cable
Twist-pair polyethylene
insulated vinyl sheath cable
(JKEV,AWG24(0.2mm
2
or more
2
))

Advertisement